Chapter 7
Settings and configuration
Kick Start
Activate the Kick Start function by entering this menu. Press
Store to save the selection.
Kick Level
Set the required level of the Kick Start. Press Store to save
the data.
This menu will only be visual if Kick Start is activated.
Kick Time
Set the required time for the kick start. Press Store to save
the data.
This menu will only be visual if Kick Start is activated.
Start Range
The ramp time for start can be set between 1 and 30 seconds
as default. If required, the range can be extended up to 120
seconds by entering this menu. Press Store to save the data.
Stop Range
The ramp time for stop can be set between 0 and 30 seconds
as default. If required, the range can be extended up to 120
seconds by entering this menu. Press Store to save the data.
The configuration of the parameters in the Start/Stop group is
now completed. It is possible to return to top level by
pressing Back three times. To configure the protection,
proceed to that menu.
93
1SFC132003M0201