Figure 35: Sequence start group
1SFC132003M0201

7:2.4.10 Sequence start

Start/Stop
The sequence start function can be used for starting several
motors or multiple speed motors with different parameter sets
such as individual ramp times, initial voltages, current limits
Torque control
etc.
Up to three individual parameter sets can be used
Protections
simultaneously.
Warnings
The LOCAL CONTROL menu can not be entered if Sequence
Faults
start is selected.
Inputs
Number of sequences (No of Seq)
Outputs
To set parameters related to a sequence start, enter the Seq
Start group.
Select the required number of parameter sets for the
Analog Output
application.
The following selections are available:
Fieldbus
No
Seq Start
2
3
Press Store to save/activate the selected function.
First sequence setting current (1st Set Ie)
Set the current for the first parameter group and press Store
to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
Second sequence setting current (2nd Set Ie)
Set the current for the second parameter group.
Press Store to save the value.
This parameter will only be displayed if parameter
No of Seq is set to 2 or 3.
If sequence start was used and the parameter No of Seq is
changed to No, the overload protection will automatically be
set to Normal independent of earlier setting.
Settings and configuration
Sequence start is not activated.
The softstarter is in normal operation.
Two different parameter sets will be used.
Three different parameter sets will be used.