1SFC132003M0201
10:76 Current limit, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Curr Lim3
This parameter makes it possible to set the current limit level
for the third parameter set.
Parameter
Default value
text
Curr Lim3
4 x I
e
10:77 Setting current, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq. Start/3rd Seq. Param./3rd Set Ie
This parameter makes it possible to set the rated motor
current for the third parameter set.
Parameter
Default value Setting range
text
3rd Set Ie
Ir
Setting range
Description
2.0...7.0 x I
Third sequence,
e
current limit
Description
9...1207A divided
Third sequence,
into 19 overlap-
motor rated cur-
ping ranges
rent
Chapter 10
Functions
171