Advertisement

1SFC132003M0201
Parameter
Default value Setting range
text
Anl Type
I Amp

10:60 Analog output, range max

Path in menu:
Menu/SETTINGS/Functional Settings/
Analog Output/ I/U/P/Q/S Range Max
With this parameter it is possible to set the value that will be
represented as the maximum value by an analog meter or by
a PLC. If for instance this parameter is set to 20000A, then 0-
20000A will be represented by 0-100% by a PLC or an
analog meter.
If the actual value happens to be greater than the selected
maximum value then the actual value will still only be
represented as the selected maximum value. This can be
useful if for instance very large currents occur during start
and only the currents during continuous run are of interest.
The possible range and the unit depend on which type of
output is selected. The range for the different output types
are listed below:
Current of the motor
Main voltage
Active power kW
Active power hp
Reactive power
Apparent power
Only the valid parameter is displayed. If for instance I Amp is
selected as output type, then only I Range Max will appear. If
TmpMot, TmpSCR or cosPhi is selected as output type, this
range parameter will not appear at all. When selecting
TmpMot or TmpSCR the range will always be 0-100% and
when selecting cosPhi the range will be 0-1.
Description
I Amp, U Volt, P
The type of
kW, P hp, Q kVAr,
value to output
S kVA, TmpMot,
from the analog
TmpSCR, cosPhi
output
I Range Max
10-20000A
U Range Max
10-1000 V
kW Range Max
1-3000 kW
hp Range Max
1-4000 hp
Q Range Max
1-3000 kVAr
S Range Max
1-3000 kVA
Chapter 10
Functions
163