ABB PST30 Installation And Commissioning Manual page 105

Softstarters
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

1SFC132003M0201
Second programmable input (In1)
Select the required function for the input In1.
One of the following functions can be selected:
None
No specific function (not activated).
Reset
Reset of an event.
Enable
When the In1=0 the softstarter stops
immediately.
When In1=1 the softstarter is in normal
operation.
Overrides all other inputs, except
LOCAL CONTROL.
Jog
Performs a start ramp until command is
released, then the motor stops immediately.
DOL
Open/close of the by-pass contactor
(PSTB370...PSTB1050).
Only if Setting I
rating.
Start3
Start signal for 3rd parameter set-up.
FB-Dis
Disable of the fieldbus communication. The
softstarter can be controlled by the hard wire
inputs instead.
Press Store to save/activate the selected function.
Caution!
The motor may start unexpectedly if there is a start signal
present when doing any of the actions listed below.
• Switching from one type of control to another (fieldbus
control / hardwire control)
• Re-programming of the programmable inputs
• Reset all Settings (programmable input set to Enable)
Chapter 7
Settings and configuration
is equal or lower than AC-3
e
105