Advertisement

1SFC132003M0201
• Current of the motor (I Amp)
• Main voltage (U Volt)
• Active power kW (P kW)
• Active power hp (P hp)
• Reactive power (Q kVAr)
• Apparent power (S kVA)
• Calculated temperature of the motor (TmpMot)
• Calculated temperature of the SCR (TmpSCR)
• Power factor (cosPhi)
Press Store to save the type of value to output.
Analog output, range (I/U/kW/hp/Q/S Range
Max)
With this parameter it is possible to set the value that will be
represented as the maximum value by an analog meter or by
a PLC. If for instance this parameter is set to 20000A, then 0-
20000A will be represented by 0-100% by a PLC or an
analog meter.
If the actual value happens to be greater than the selected
maximum value then the actual value will still only be
represented as the selected maximum value. This can be
useful if for instance very large currents occur during start
and only the currents during continuous run are of interest.
The possible range and the unit depend on which type of
output is selected. The range for the different output types
are listed below:
Current of the motor I Range Max
Main voltage
U Range Max
Active power kW
kW Range Max
Active power hp
hp Range Max
Reactive power
Q Range Max
Apparent power
S Range Max
Only the valid parameter is displayed. If for instance I Amp is
selected as output type, then only I Range Max will appear. If
TmpMot, TmpSCR, or cosPhi is selected as output type, this
range parameter will not appear at all. When selecting
TmpMot or TmpSCR the range will always be 0-100% and
when selecting cosPhi the range will be 0-1.
Press Store to save the range of output.
Chapter 7
Settings and configuration
10...20000 A
10...1000 V
1...3000 kW
1...4000 hp
1...3000 kVAr
1...3000 kVA
109