Chapter 7
Settings and configuration
Setting Ie
100A
Store
Figure 16: Setting Ie menu
Setting Ie
100A
Next
Back
Figure 17: Confirming Setting Ie
OL Class
10
Store
Figure 18: Overload class
OL Class
Next
Back
Figure 19: Confirming OL Class
Ext ByPass
Yes
Store
Figure 20: External ByPass
Ext ByPass
Next
Back
Figure 21: Confirming Ext ByPass
Ready?
Yes
Tune Set
Figure 22: Ready?/Tune Set menu
88
10
Yes
Setting I
e
Set the current that the softstarter will be exposed to i.e.
rated motor current if the unit is connected In Line.
For units connected Inside Delta the Setting I
according to the current in the delta circuit = 58% (
of the rated motor current.
Press Store to save the data after setting the current.
Confirm the Setting I
by pressing Next. If wrong Setting I
e
was set, press Back and set the correct value.
Overload class (OL Class)
Select the class for the overload relay for the used
application type. Available classes:
• 10A
• 10
• 20
• 30
Press Store to save the selected class.
Confirm the selected overload class by pressing Next. If
wrong overload class was selected, press Back and select
the correct class.
External By-Pass contactor (Ext ByPass)
If an external by-pass contactor is used, set the parameter to
Yes, otherwise No.
Press Store to save the data.
Confirm the selection of external by-pass by pressing Next. If
wrong selection was made, press Back and correct the
selection.
Tune Set
The configuration of the application setting menu is now
completed. If no tuning of the settings is wanted, it is possible
to return to the top level by pressing Yes.
If tuning of some main parameters is wanted, select Tune
Set.
must be set
e
)
(
)
1
3
e
1SFC132003M0201