10:58 Analog output, reference
Path in menu:
Menu/SETTINGS/Functional Settings/
Analog Output /Anl Ref
With this parameter it is possible to set the unit and the range
of the signal to output. This selected range will be the
physical output from the softstarter. This range should be
selected to suit the analog meter or the PLC that uses this
signal as its input. The possible options are:
• 0-10 V
• 0-20 mA
• 4-20 mA
If for instance 4-20 mA is selected, then this range will
represent 0-100% of the output signal, for instance the
current of the motor.
Parameter
Default value Setting range
text
Anl Ref
4...20 mA
10:59 Analog output, type of value
Path in menu:
Menu/SETTINGS/Functional Settings/
Analog Output /Anl Type
With this parameter it is possible to set which type of value
that should be the output of the analog output. The possible
types of values are:
I Amp
Current of the motor
U Volt
Main voltage
P kW
Active power kW
P hp
Active power hp
Q kVAr
Reactive power
S kVA
Apparent power
TmpMot
Calculated temperature of the motor
TmpSCR
Calculated temperature of the SCR
cosPhi
Power factor
Description
0...10V, 0...20mA,
The type of the
4...20mA
output signal of
the analog out-
put