Param.
Description
number
1
Setting current
2
Start ramp
3
Stop ramp
4
Initial voltage
5
End voltage
6
Step down voltage
7
Current limit
8
Kick start
9
Kick start level
10
Kick start time
11
Start ramp range
12
Stop ramp range
13
Overload protection type
14
Overload protection class
15
Overload class, dual type, start class
16
Overload class, dual type, run class
17
Overload protection, type of operation
18
Locked rotor protection
19
Locked rotor protection level
20
Locked rotor protection time
21
Locked rotor protection, type of operation
22
Underload protection
23
Underload protection level
24
Underload protection time
25
Underload protection, type of operation
26
Phase imbalance protection
27
Phase imbalance protection level
28
Phase imbalance protection, type of opera-
tion
29
High current protection
30
High current protection, type of operation
31
Phase reversal protection
32
Phase reversal protection, type of operation
33
PTC protection
34
PTC protection, type of operation
35
External by-pass
37
High current warning
38
High current warning level
39
Low current warning
40
Low current warning level
41
Overload warning
42
Overload warning level
43
Thyristor (SRC) overload warning
44
Phase loss fault, type of operation
45
Fieldbus fault, type of operation
46
Frequency fault, type of operation
47
Heat sink over-temperature fault, type of
operation
48
Thyristor short circuit fault, type of operation
49
Function of programmable input In0
1SFC132003M0201

7:1.2 Parameter list

Display text
Setting Ie
Start Ramp
Stop Ramp
Init Volt
End volt
Step down
Current Lim
Kick Start
Kick Level
Kick Time
Start Range
Stop Range
Overload
OL Class
OL Class S
OL Class R
OL Op
Locked Rotor
Lock R Lev
Lock R Time
Lock R Op
Underload
Underl Lev
Underl Time
Underl Op
Phase Imb
Ph Imb Lev
Ph Imb Op
High I
High I Op
Phase Rev
Ph Rev Op
PTC
PTC Op
Ext ByPass
Warn I=High
Wa I=H Lev
Warn I=Low
Wa I=L Lev
Warn OL
Wa OL Lev
Warn SCR OL
Ph Loss Op
FB Fault Op
Freq F Op
HS Temp Op
SCR SC Op
In0
Settings and configuration
Setting range
9.0...1207A
1...30s, 1...120s
0...30s, 0...120s
30...70%
30...70%
30...100%
2.0...7.0xle
Yes, No
50...100%
0.1...1.5s
1-30s, 1-120s
0-30s, 0-120s
No, Normal, Dual
10A, 10, 20, 30
10A, 10, 20, 30
10A, 10, 20, 30
Stop-M, Stop-A, Ind
Yes, No
0.5...8.0xle
0.2...10s
Stop-M, Stop-A, Ind
Yes, No
0.4...0.8xle
1...30s
Stop-M, Stop-A, Ind
Yes, No
10...80%
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A, Ind
Yes, No
Stop-M, Stop-A, Ind
Yes, No
Yes, No
0.5...5.0xle
Yes, No
0.4...1.0xle
Yes, No
40...99%
Yes, No
Stop- M, Stop-A
Stop- M, Stop-A
Stop- M, Stop-A
Stop- M, Stop-A
Stop- M, Stop-A
None, Reset, Enable
Jog, DOL, Start 2, FB-
Dis
Chapter 7
Default
Actual
value
setting
Individual
10s
0s
30%
30%
100%
4.0xle
No
50%
0.2s
1-30s
0-30s
Normal
10
10
10
Stop-M
No
4.0xle
1.0s
Stop-M
No
0.5xle
10s
Stop-M
No
80%
Stop-M
No
Stop-M
No
Stop-M
No
Stop-M
No
No
1.2xle
No
0.8xle
No
90%
No
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Reset
81