to ground, the control will shut down the unit, triggering the 0x0200 Dc Protection alarm.
In 250 to 625 kW TL models in which the MS option has been added, the 4-pole thermomagnetic circuit breaker
shall be placed in cubicle A.
5.6.2. Remote triggering kit
In some countries, current regulations require remote protection to be implemented in inverters to open the connec-
tions. To achieve this a kit may be used which opens the thermomagnetic circuit breaker on the grid connection.
To activate the coils that make the thermomagnetic circuit breakers open, just close a volt-free contact in the remote
activation terminals. The contact must be able to work with 230 Vac 50 Hz and a power of 40 VA.
The remote activation terminals are placed in cubicle D (Ac module), next to terminal 220.