5.6. Available kits

The main kits that can be added to the various versions of IngecOn Sun PowerMax.

5.6.1. grounding kit

The PV array is grounded by a thermomagnetic circuit breaker that connects one pole of the PV array, negative or
positive, to ground. The polarity of the connection depends on the type of panel technology.
each MPPT can have only one ground reference, so this kit can only be installed on IngecOn Sun PowerMax
inverters with the master-slave option.
+PV
8xZDU 10
-PV
8xZDU 10
Q7
S804 UC-B10
The thermomagnetic protection will open the PV array connection to ground when an insulation fault in the PV array
generates a current through the connection which is greater than the protection's tripping current.
The current generated by the panels is closed by the lack of a positive pole, closing via the negative pole connection,
until it returns to the panel. When the current exceeds the thermal value of the protection (10 A), the circuit is opened
and current ceases to flow to ground.
60
S804 UC-B10
+PV
8xZDU 10
-PV
8xZDU 10
Q7
S804 UC-B10
current present
+PV
8xZDU 10
-PV
8xZDU 10
Q7
Installation manual
AAV2000IKI01