Access points common to all Ingecon Sun PowerMax units

Access for communication cables or auxiliary inputs is located on the left side of the Dc cabinet in all versions.
each gland allows for a range of cable diameters:
The tapered grommets allow wire diameter of up to 40 mm.
care must be taken to ensure the equipment is not live when accessing its interior.
All the doors on the cabinet are arranged so that they can only be opened when the Ac
thermomagnetic circuit breaker, the Dc isolating switch and any auxiliary external supplies are
disabled.
When checking that there is no voltage, wearing dielectric gloves and safety goggles approved for
electrical hazards is required.
While the door is open, do not alter the position of the thermomagnetic circuit breaker or isolating switch, do not
operate the controls on the door nor apply force to the internal electrical devices which they control.
They must also be in the OFF position for the door to be able to be closed.
After setting the Ac thermomagnetic circuit breaker, the Dc isolating switch and any auxiliary external supplies to OFF,
wait at least 10 minutes before opening the door. Internal capacitances may still hold hazardous voltages.
During inspection and handling work:
Take care, since even with the Ac thermomagnetic circuit breaker and the Dc isolating switch on OFF, cables directly
connected to the grid or panels may still have dangerous voltages. This includes feed strips and wires between
switches/breakers.
As long as the panels are exposed to the light, the Dc cables will carry potentially dangerous voltage levels.
AAV2000IKI01
gland diameter (mm)
40
16
12
cable diameter (mm)
19 ~ 28
4.5 ~ 10
3.5 ~ 7
Ingeteam