INGECON SUN Power U
Outdoor
Installation manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUN 125 U 208 Outdoor and is the answer not in the manual?

Questions and answers

Summary of Contents for Ingecon SUN 125 U 208 Outdoor

  • Page 1 INGECON SUN Power U Outdoor Installation manual...
  • Page 2 Ingeteam Inc ABB2000IKI01_B 05/2013 3550 W. Canal St. Milwaukee, WI 53208 - USA Tel.: +1 (414) 934 4100 Fax.: +1 (414) 342 0736 e-mail: solar.us@ingeteam.com Service Call Center: +1 (414) 934 4158 The copy, distribution or use of this document or of its content requires written authorisation. Any breach thereof will be reported for damages.
  • Page 3 Important safety precautions This manual contains important instructions for the installation, handling and use of the following models: Units with a transformer INGECON SUN 125 U 208 Outdoor INGECON SUN 125 U 480 Outdoor Units without a transformer INGECON SUN 125 TL U 208 Outdoor...
  • Page 4 Ingeteam Installation manual Carry out all control and handling without voltage. As a minimum security measure in this operation, the so-called five golden rules should always be followed: Disconnect Prevent any possible resupply Check there is no voltage Ground and short circuit the equipment Protect from live elements, if any, and put up safety signs around the work zone.
  • Page 5 Installation manual Ingeteam Potential hazards for the equipment Bear in mind the following warnings concerning protection of the equipment. CAUTION: Ventilation. The unit requires quality air flow while it is operating. Keeping the unit in the upright position and the inlets free of obstacles is essential for this air flow to reach the inside.
  • Page 6 Ingeteam Installation manual Cabling and torque requirements Connection to the PV array must be with the following minimum types of cable; the maximum for input terminals is DC 250 kcmil (0.2 in , 127 mm ) and for output terminals AC 300 kcmil (0.24 in , 152 mm Tightening torque St.st.
  • Page 7 Reference Quantity INGECON SUN 125 U 208 Outdoor INGECON SUN 125 U 480 Outdoor INGECON SUN 208 V 3 ph electronics block INGECON SUN 480 V 3 ph electronics block R1, R2, R3 Tubular silicon power resistor 200 W C1, C2, C3...
  • Page 8 Ingeteam Installation manual Units without a transformer INGECON SUN 125 INGECON SUN 165 INGECON SUN 200 INGECON SUN 220 Reference Quantity TL U 208 Outdoor TL U 275 Outdoor TL U 330 Outdoor TL U 360 Outdoor INGECON SUN INGECON SUN...
  • Page 9 Installation manual Ingeteam Symbols on the inverters Warning symbols on the inverter are as follows: Ø 1 Connection from cable and phase 1 terminal. Ø 2 Connection from cable and phase 2 terminal. Ø 3 Connection from cable and phase 3 terminal. DC outlet.
  • Page 10 Ingeteam Installation manual WARNING RISK OF ELECTRIC SHOCK DO NOT REMOVE COVER. No user serviceable parts inside. Refer servicing to qualified service personnel. WARNING RISK OF ELECTRIC SHOCK FROM ENERGY IN CAPACITOR. Do not remove cover until 5 minutes after disconnecting all sources of supply.
  • Page 11: Table Of Contents

    Installation manual Ingeteam Table of Contents 1. Overview ...............................14 1.1. Equipment description ........................14 1.1.1. Models ..........................14 1.1.2. Options ..........................14 1.2. Configuration parameters ........................15 1.2.1. Units with a transformer ......................15 1.2.2. Units without a transformer (TL) ....................16 1.3. Compliance with regulations ......................17 2.
  • Page 12 Ingeteam Installation manual 5.5.10. Connection for Ethernet communication .................50 5.5.11. Ground connections ......................50 5.5.12. Grid connection ........................51 5.5.13. Connecting to the PV array ....................53 Units fitted with ground connection on the positive pole ..............54 Units fitted with ground connection on the negative pole ..............54 Non-grounded units ........................55 5.6.
  • Page 13 Installation manual Ingeteam External to the unit ........................80 Internal to the unit ........................80 9.4.7. Manual shutdown ........................81 9.4.8. Protection of the switching filter ....................81 9.5. Replacing the electronics block ......................81 9.6. Replacing varistors in the intake board .................... 83 9.7. Description of terminal strip ......................84 ABB2000IKI01 xiii...
  • Page 14: Overview

    Ingeteam Installation manual 1. Overview The purpose of this manual is to describe the INGECON SUN Power U and to give appropriate information for its correct receipt, installation, start-up, maintenance and operation. 1.1. Equipment description An inverter is a circuit used to convert direct current to alternating current. The function of these units is to convert the direct current generated by photovoltaic solar panels to alternating current and so enable it to be fed to the elec- tricity grid.
  • Page 15: Configuration Parameters

    Installation manual Ingeteam 1.2. Configuration parameters 1.2.1. Units with a transformer DC input 125 U 208 125 U 480 Range of input operating voltage 330 ~ 920 V Maximum input voltage 1000 V Maximum input current 390 A Maximum input short circuit current 250 A (4 fused inputs) Maximum input source backfeed current to input source AC output...
  • Page 16: Units Without A Transformer (Tl)

    Ingeteam Installation manual 1.2.2. Units without a transformer (TL) DC input 125 TL U 208 165 TL U 275 200 TL U 330 220 TL U 360 Range of input operating voltage 330 ~ 920 V 440 ~ 920 V 525 ~ 920 V 570 ~ 920 V Maximum input voltage...
  • Page 17: Compliance With Regulations

    Installation manual Ingeteam 1.3. Compliance with regulations UL 1741 UL Standard for Safety for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources, Second Edition, Dated Janauary 28, 2010. CAN/CSA-C22.2 No. 0-M91 - General Requirements - Canadian Electrical Code - Part II. 0.4-04 - Bonding of Electrical Equipment.
  • Page 18: Atmospheric Conditions

    Ingeteam Installation manual 2.1.4. Atmospheric conditions The ambient air must be clean and relative humidity must not exceed 50% at over 104 °F (40 °C). Higher levels of relative humidity, up to 95%, can be tolerated at below 86 °F (30 °C). It should be borne in mind that moderate condensation may occasionally occur as a consequence of temperature variations.
  • Page 19: Environmental Characteristics

    Installation manual Ingeteam 2.1.8. Environmental characteristics The environmental conditions for operation are: Ambient conditions Minimum temperature -4 °F (-20 °C) Minimum surrounding air temperature -4 °F (-20 °C) Minimum surrounding air temperature 149 °F (65 °C) Temperature at which power limiting commences 122 °F (50 °C) Maximum relative humidity without condensation Units including a heating element kit may be installed in locations with a minimum temperature of -13 °F (-25 °C).
  • Page 20 Ingeteam Installation manual INGECON SUN 125 U 208 Outdoor Shock absorbing Electronics block resistors EMI AC filter DC fuses Harmonic filter DC plates SAC* Electronics block AC AC contactor plates EMI DC filter AC arresters EMC filter AC thermomagnetic circuit breaker...
  • Page 21 Installation manual Ingeteam INGECON SUN 125 U 480 Outdoor Shock absorbing Electronics block resistors EMI AC filter DC fuses Harmonic filter DC plates SAC* Electronics block AC AC contactor plates EMI DC filter AC arresters EMC filter AC thermomagnetic DC breaker...
  • Page 22 Ingeteam Installation manual INGECON SUN 125 TL U 208, 165 TL U 275, 200 TL U 330 y 220 TL U 360 Outdoor Shock absorbing Electronics block resistors DC fuses Harmonic filter DC plates Electronics block AC AC contactor plates...
  • Page 23: Operating, Conservation And Transport Conditions

    Dimensions Model Packing pallet Weight (H x W x D) Units with a transformer INGECON SUN 125 U 208 Outdoor Bubble wrap and plastic bag on 2601.45 lb 85.04 x 49.6 x 39.37 in wooden pallet (1180 kg) (2160 x 1260 x 1000 mm)
  • Page 24: Handling And Unpacking

    Tel.: +1 (415) 450 1869 Master Project: XXXXXX +1 (415) 450 1870 Fax.: +1 (408) 824 1327 File Number: XXXXXX e-mail: solar.us@ingeteam.com INGECON SUN 125 Model/ Type Date of Manufacture 2012/03 TL U 208 Outdoor Normal operating -4 °F (-20 °C) ~...
  • Page 25: Moving The Equipment

    Installation manual Ingeteam 3.4. Moving the equipment Appropriate transport and storage of the unit are the necessary first steps for correct use and operation. Taking the above section into account and as a preventive measure, Ingeteam recommends the use of transport companies specialized in the transport of special and/or fragile equipment.
  • Page 26: Storage

    Ingeteam Installation manual Transport using a crane When moving with a crane, use the strips supplied for this purpose. To access these: Remove the side roofs of the unit by removing the 4 bolts on each side as shown below: Turning the lateral metal sheet will reveal the strips supplied for moving the unit with a crane.
  • Page 27: Conservation

    Installation manual Ingeteam Environmental characteristics”. • It is very important to protect the unit from chemical products which can cause corrosion, as well as from salty atmospheres. • Do not store the unit outdoors. 3.6. Conservation In order to permit correct conservation of the units, they must not be removed from their original packaging until it is time to install them.
  • Page 28: Safety Instructions

    Ingeteam Installation manual 4. Safety instructions This section contains safety instructions which must be followed when installing, operating and accessing the unit. Failure to comply with the Safety instructions may cause injury or even death or cause damage to the unit. Read the Safety instructions carefully before working on the unit.
  • Page 29: General

    Installation manual Ingeteam The electrical installation must not involve a risk of fire or explosion. Workers must be duly protected against accident risks from direct or indirect contact. The electrical installation and protection devices must take the voltage, the external determining factors and the competence of the people who have access to parts of the installation into account.
  • Page 30: General Risks Existing And Preventive Measures

    Ingeteam Installation manual 4.3.1. General risks existing and preventive measures Impact against immovable objects • Inform workers of the risk • Adequate lighting • Work with care • Keep sufficient distance to prevent contact with the part causing the risk (control rod in the isolating switch door).
  • Page 31: Personal Protection Equipment (Ppe)

    Installation manual Ingeteam 5 GOLDEN RULES Disconnect Switching on the possible voltage sources. Bear in mind that any capacitors or other elements powered from uninterruptible power supplies (UPS) are still live. Prevent any possible feedback. The switching devices used to switch off the equipment must be protected against any possible reconnection.
  • Page 32 Ingeteam Installation manual Open the thermomagnetic circuit breaker (*). Isolate the PV array powering the unit, from outside the panel. (**) Switch off three-phase protection from the corresponding protection outside the units. Open the QAUX switch. Wait 10 minutes for the internal capacitances to discharge (harmonic filter, etc.), for the existing internal resistors to cool and the fan blades to stop turning.
  • Page 33: Installation

    Installation manual Ingeteam 5. Installation Before installing the unit, the packaging must be removed, taking special care not to damage the housing. Check that there is no moisture inside the packaging. If there are signs of moisture, the unit must not be installed until you are sure it is completely dry.
  • Page 34 Ingeteam Installation manual ≥ 0.32 in (8 mm) ≥ 2.84 in (72 mm) ABB2000IKI01...
  • Page 35 Installation manual Ingeteam The dimensions of the unit are as follows. Bear in mind the clearance between the pins of the fixing strips and the floor (if they are fitted): 47.7 in 32.08 in (1212 mm) (815 mm) SECTION A-A CORTE A-A 49.76 in (1264 mm)
  • Page 36: Requirements For Transformers And Insulation Monitor

    INGECON SUN Power U inverters connected to the inverter’s low voltage winding must be synchronized. MPPTs connected via INGECON SUN Power U to the same transformer must have the same voltage settings. The Ucc short circuit voltage of the transformer must be equal or less than 6%.
  • Page 37: Insulation Monitor (Units Without An Ungrounded Transformer)

    Installation manual Ingeteam The primary circuit is connected to the power input. We recommend installing protection and switching components to protect this transformer. The technical requirements of the auxiliary transformer are: The transformer’s power should be suitable for the loads connected to it. Take into account the environ- mental conditions of the site.
  • Page 38: Description Of Cable Inlets

    Ingeteam Installation manual After setting the AC thermomagnetic circuit breaker and DC circuit breaker to OFF, wait at least 10 minutes before opening the door. Internal capacitances may still hold hazardous voltages. Once the equipment is open, check there is no electrical hazard in the voltage inputs from the grid, the PV array or any auxiliary supply.
  • Page 39: Description Of Cabling Connections

    Installation manual Ingeteam Opening the inside doors of the cabinet is conditional on both the AC thermomagnetic circuit breaker and the DC circuit breaker being in the open position. When checking that there is no voltage, wearing dielectric gloves and safety goggles approved for electrical hazards is required.
  • Page 40: Inverter Wiring Diagram

    Ingeteam Installation manual 5.5.4. Inverter wiring diagram Units with a transformer and positive grounding Fuse AC thermomagnetic circuit DC breaker Inverter Contactor breakers Fuses Transformer AC surge arresters DC surge arresters Units with a transformer and negative grounding Fuses AC thermomagnetic circuit DC breaker Inverter Contactor...
  • Page 41 Installation manual Ingeteam Units without a transformer (TL) and negative grounding Fuses AC thermomagnetic circuit DC breaker Inverter Contactor breakers Transformer AC surge arresters Fuse DC surge arresters ABB2000IKI01...
  • Page 42: System Wiring Diagram

    Ingeteam Installation manual 5.5.5. System wiring diagram The various grid connection options are described below. ELECTRICAL DIAGRAM FOR UNITS WITH TRANSFORMERS INGECON SUN Power U Non-grounded units INGECON SUN Power U Units with negative grounding INGECON SUN Power U Units with positive grounding...
  • Page 43 Installation manual Ingeteam Wiring diagram for units without a transformer (TL) INGECON SUN Power TL U Non-grounded units INGECON SUN Power TL U Units with negative grounding INGECON SUN Power TL U Units with positive grounding ABB2000IKI01...
  • Page 44 Ingeteam Installation manual Wiring diagram for synchronized units without a transformer (TL) INGECON SUN Power TL U INGECON SUN Power TL U Up to 6 units INGECON SUN Power TL U Non-grounded units ABB2000IKI01...
  • Page 45 Installation manual Ingeteam INGECON SUN Power TL U INGECON SUN Power TL U Up to 6 units INGECON SUN Power TL U Units with negative grounding Units without a transformer with negative grounding cannot be synchronized. ABB2000IKI01...
  • Page 46 Ingeteam Installation manual INGECON SUN Power TL U INGECON SUN Power TL U Up to 6 units INGECON SUN Power TL U Units with positive grounding Units without a transformer with positive grounding cannot be synchronized. ABB2000IKI01...
  • Page 47: Insulation Fault Contact / Grid Connection Indicator

    Installation manual Ingeteam INGECON SUN Power TL U INGECON SUN Power TL U Up to 6 units INGECON SUN Power TL U Units with various grounding polarities Units without a transformer with various polarity grounding cannot be synchronized. 5.5.6. Insulation fault contact / grid connection indicator The inverter incorporates a normally open volt-free auxiliary contact.
  • Page 48: Access To Auxiliary Connections

    Ingeteam Installation manual 1 ... 16 1 ... 12 0 ... 4 5.5.7. Access to auxiliary connections Some PV installations require the inverter to be connected to auxiliary equipment, such as solar radiation sensors, heat sensors and anemometers. Consult the manufacturer when ordering. For best performance, the cables carrying these auxiliary signals will be removed from the power cables.
  • Page 49 Installation manual Ingeteam Connect the rod cable to the cable’s rod output, and feed it out through the holes on the upper left side of the enclo- sure. Connect the end that goes outside to the rod and attach it via its magnet to the unit’s enclosure. See AAX2002IKI01 Installation Guide for Communications Devices”.
  • Page 50: Connection For Ethernet Communication

    Ingeteam Installation manual 5.5.10. Connection for Ethernet communication At the request of the installer, inverters may optionally incorporate hardware for communicating via ethernet. This hardware is made up of an “AAX0004 Com Ethernet + RS-485” board. The unit is provided with a >211 Ohm ferrite rod. The cable coming from the “AAX0004 Com Ethernet + RS-485”...
  • Page 51: Grid Connection

    Installation manual Ingeteam 5.5.12. Grid connection The cables for connecting the unit to the grid enter through conduits at the base of the cabinet. They must withstand at least the phase voltage and 1000 V between a phase and ground. These units have three strips (phases) and a terminal (N) for connection to the grid.
  • Page 52 XAC terminal strip between terminals 0 and 1, as shown in the following figure. 1 ... 16 1 ... 12 0 ... 4 Ingeteam recommends a star connection for the transformer for INGECON SUN Power U units. ABB2000IKI01...
  • Page 53: Connecting To The Pv Array

    Installation manual Ingeteam 5.5.13. Connecting to the PV array The cables for connecting the unit to the PV array enter through conduits in the base. Before any handling, check that there is no electrical hazard in the voltage input from the PV array. Never forget that whenever they receive solar radiation, the panels’...
  • Page 54: Units Fitted With Ground Connection On The Positive Pole

    Ingeteam Installation manual Units fitted with ground connection on the positive pole In this case the positive polarity of the PV array should be connected to the strip corresponding to the grounded side and the negative polarity to the strips corresponding to the non-grounded side. Positive pole Negative pole Check the existence of a grounding fuse.
  • Page 55: Non-Grounded Units

    Installation manual Ingeteam Non-grounded units IN this case the connection should be the same as for units with negative grounding. Check for the absence of a grounding fuse. See “2.4. Location of the components”. Negative pole Positive pole 5.6. Available kits The main kits that can be added to the various versions of the equipment are shown below.
  • Page 56: Remote Triggering Kit

    The contact must be able to work with 220 ~ 240 Vac 50/60 Hz and 150 VA power, except for the INGECON SUN 125 U 480 Outdoor, where the power is 50 VA. This kit does not provide remote resetting. The unit must be reconnected manually.
  • Page 57: Auxiliary Services Kit

    The purpose of this kit is to generate the necessary supply for the operation of the inverter’s auxiliary services, thus avoiding the need to supply the unit externally. This kit comprises a transformer with a suitable ratio for each model in the INGECON SUN Power U family. Auxiliary service transformer 5.6.5.
  • Page 58: Synchronization Kit

    24/06/12 24/06/12 5.6.6. Synchronization kit When several INGECON SUN Power TL U units are connected to the same medium voltage transformer, they must be synchronized. Care must be taken to ensure the equipment is not live when accessing its interior.
  • Page 59 Installation manual Ingeteam In this type of configuration the PV array may be grounded. In this example the synchronization signal in generated in the synchronization kit, located in the lower right-hand corner of the intake board, and which distributes the signal to 4 units (maximum 6). The inverters are connected via the fiber optic cables supplied.
  • Page 60: Commissioning

    Ingeteam Installation manual 6. Commissioning 6.1. Equipment inspection The units are equipped with a series of thermomagnetic circuit breakers to protect their various components. These should be closed prior to unit start-up. Before working on the thermomagnetic circuit breakers, check that there are no electrical hazards inside the unit.
  • Page 61: Start-Up

    Installation manual Ingeteam 6.2. Start-up First carry out a general visual inspection and wiring check, then proceed to connect power to the unit while keeping it switched off, following the guidelines in the instruction manual of the unit. The tasks outlined for this step must be carried out with the unit door always closed, thus avoiding possible contact with live parts without NEMA 3R protection.
  • Page 62: Preventive Maintenance

    Ingeteam Installation manual 7. Preventive maintenance The recommended preventive maintenance tasks must be carried out at least annually, except for the checking the fans and filters, which must be done monthly. The various maintenance tasks must be performed by qualified personnel. Danger of electric shock. To access the various compartments, take into account the safety recommendations in previous chapters.
  • Page 63 Installation manual Ingeteam Ensure adequate ventilation of the unit Checking the status of exhaust fans, cleaning and replacing them if necessary. The useful life of the fans is 4 years, so they must be replaced after this time even if they seem to be functioning normally.
  • Page 64 Ingeteam Installation manual Every three months the filters must be removed for cleaning. The figure below shows how to remove them (there is a filter with similar characteristics fitted on the opposite side of the unit). Filter In order to keep the nuts and bolts of the equipment in a proper condition, it is important while tight- ening them to make sure there is no dirt or shavings on the threads and to apply a suitable lubricant.
  • Page 65: Display Control

    Installation manual Ingeteam 8. Display control These inverters incorporate a display and keypad unit to interface with the installer and the user. This interface allows the display of the main internal parameters and the configu- ration of the entire system during installation. Parameters, variables and commands are organized as menus and submenus.
  • Page 66: Display

    Ingeteam Installation manual 8.2. Display The current date and time on the top line. The internal clock 17:05 17:05 24/06/12 24/06/12 automatically changes the time from summer to winter and vice versa. NODO 1 NODO 1 99,2kW 99,2kW The node number for which data is being viewed appears 229V 229V beneath the top line on the left.
  • Page 67: Main Menu

    Installation manual Ingeteam 8.3. Main menu The main menu contains the following submenus: 17:05 17:05 24/06/12 24/06/12 • Monitoring. This displays the main internal parameters and variables that indicate the operation status of the unit. • Reasons for shutdown. This option shows the reasons why the inverter was shut down the last five times.
  • Page 68: Reasons For Shutdown

    Ingeteam Installation manual Screen 5 Impedance of the entire PV array to ground. Rpv+ Impedance of the positive pole of the PV array to ground. Rpv- Impedance of the negative pole of the PV array to ground. Screen 6 Alarms Status of inverter alarms.
  • Page 69: Settings

    Installation manual Ingeteam MP VIN High input voltage from the panels. MP FRED Incorrect grid frequency. MP VRED Incorrect grid voltage. MP VARISTORES Varistor fault. MP AISL.DC DC insulation fault. MP INT AC RMS Continuous overvoltage on AC output. MP TEMPERATURA Overtemperature in the power electronics.
  • Page 70: Grid Quality

    Ingeteam Installation manual 17:05 17:05 24/06/12 24/06/12 English English Press the button to scroll through the various languages and to confirm the selection. Grid quality In this menu, you can change the grid quality parameters. This menu is only active after the security code has been input.
  • Page 71: Change Inverter Number

    9.1. LED messages Some of the LEDs indicate some kind of problem in the PV installation. Display INGECON SUN Power U 9.1.1. Green LED This is the LED that should light up in normal start-up and operating conditions, while the others remain off. It has...
  • Page 72: Orange Led

    Ingeteam Installation manual 9.1.2. Orange LED This LED indicates that alarms have been set off in the inverter. Fast flashing This flashing indicates that an alarm has occurred in the inverter, but the anomaly in the operation does not require stopping the inverter.
  • Page 73: List Of Alarms And Reasons For Shutdown

    Installation manual Ingeteam 9.2. List of alarms and reasons for shutdown The following table details the possible reasons for each alarm. Code Alarm Reason for shutdown Description 0000H None No alarm, the unit must be connected whenever it has enough power. 0001H Frequency Grid frequency out of range.
  • Page 74: Inverter Alarms Due To Protections

    Ingeteam Installation manual 9.3. Inverter alarms due to protections Code Description This alarm goes off when an AC protection element is triggered. The items monitored are: , RV Which are the protections for the filters and AC intakes and DC intakes and contactor. In normal operation, all contacts should be closed, except for the contactor circuit.
  • Page 75: Voltage And/Or Frequency Out Of Range

    Installation manual Ingeteam Only in the event of an insulation fault triggered by alarm 0400H will the AC power be switched off and the DC power be left. Open the unit and find the section in this guide that deals with the alarm or reason for shutdown recorded in the first step.
  • Page 76 Ingeteam Installation manual The figure has verified the resistance of phase 1, L1. Testing required for L2 and L3. Check for continuity between Rcapt, Scapt and Tcapt terminals of the inverter’s Q4 thermomagnetic circuit breaker and XAC terminal strip on the electronics block, according to the following sequence of terminals (see figure): •...
  • Page 77: Temperature

    Installation manual Ingeteam J11 J10 Intake board 9.4.2. Temperature Code Alarm Reason for shutdown Description 0020H Temperature Power electronics temperature. The power electronics exceeds 176 °F (80 °C). Auxiliary temperature sensor The auxiliary temperature sensor has triggered an alarm In the event of a shutdown with reason “Motivo Paro Temperatura”, the first step is to check if the 0020H alarm persists.
  • Page 78: Ac Circuit Protection

    Ingeteam Installation manual thermal switch built into the inverter in the radiator of the electronics block. • If the displayed temperature is abnormally low (compared to room temperature), the root of the problem could be with the NTC built into the inverter. Checking the NTC To check the NTC of the unit you will need to access the J18 terminal of the intake board.
  • Page 79: Reason For Contactor Shutdown

    Installation manual Ingeteam AC PROTECTION Consists of thermomagnetic circuit breakers Q1, Q2, QAUX and Q4. X7.2 X3.4 AC ARRESTER Consists of RVAC. RVAC X7.1 X3.3 To check the AC protection branch, you should see continuity between the ends of the monitoring circuit: Q1 11 and Q2 14.
  • Page 80: External To The Unit

    Ingeteam Installation manual External to the unit Non-grounded units To check whether the insulation fault is external to the unit, see whether the Rpv+ and Rpv- impedances are displayed on the display screen (selecting the fifth screen from the monitoring menu). Given an insulation fault, one or both will be 0 or a low figure.
  • Page 81: Manual Shutdown

    Installation manual Ingeteam 9.4.7. Manual shutdown Code Alarm Reason for shutdown Description 1000H Manual shutdown Manual shutdown Manual shutdown due to the limit switch, via the display or communications To verify that the limit switch works properly, check for continuity between terminals X2.1 and J17.1, and between terminals X2.2 and J17.2.
  • Page 82 Ingeteam Installation manual The electronics block is a heavy element. We suggest that it be carried by two people or with mechan- ical assistance. When handling the block, personal protective equipment (PPE) must be worn: helmet, glasses and safety footwear. The tools needed to replace the electronics block are: •...
  • Page 83: Replacing Varistors In The Intake Board

    Installation manual Ingeteam Connect the “Power cables” at the bottom of the block. Connecting the unit to the PV array. 9.6. Replacing varistors in the intake board The varistor is connected to the 3-pin connector on pins 1 and 2. Pin 3 is for connecting the thermal fuse. The varistor must be connected as follows: •...
  • Page 84: Description Of Terminal Strip

    Ingeteam Installation manual 9.7. Description of terminal strip The terminal strip is made up of type ZKS plug-in connectors and type WDU screw-in terminals. 1 ... 16 1 ... 12 0 ... 4 X1.1 Free X1.2 Free XFN Nighttime power supply connection XFN.1 + nighttime supply XFN.2...
  • Page 85 Notes...
  • Page 86 Notes...
  • Page 87 Notes...
  • Page 88 Ingeteam Power Technology, S.A. Energy Avda. Ciudad de la Innovación, 13 31621 SARRIGUREN (Navarre) - Spain Tel: +34 948 28 80 00 Fax: +34 948 28 80 01 e-mail: solar.energy@ingeteam.com ABB2000IKI01_B Ingeteam S.r.l. 05/2013 Via Emilia Ponente, 232 48014 CASTEL BOLOGNESE (RA) - Italy Tel: +39 0546 651 490 Fax: +39 054 665 5391...