5.4.7. connection for communication via RS-485 serial port

TheseIngecOn Sun PowerMax units incorporate hardware for communicating via an RS-485 serial line. This
hardware comprises two to four "AAP0022 com RS-485" boards (one per module) that are supplied mounted on the
control board in each power block, the communications terminal strip and the wiring between boards and terminal
strip.
Thanks to this pre-installation, the installer will only need to make the connection via the terminal, located as shown
in the following figure in the Dc module at the top of the sidewall.
To access this terminal, use the access openings in this area of the enclosure.
The unit is provided with a >211 Ohm ferrite rod. The cable connecting the "AAP0022 com RS-485"
board of the first electronics block to the terminals must be inserted as close as possible to the board,
turning it around the centre hole twice.
For more information on board operation, see "AAX2002IKI01 Installation guide for communications Devices".

5.4.8. connection for communication via modem-gSM/gPRS + RS-485

At the request of the installer, inverters may optionally be equipped with hardware for communication via gSM/gPRS
phone. This hardware comprises one to three "AAP0022 com RS-485" boards (one per module except for module
1) that are supplied mounted on the control board in each power block, a "AAX0001 com gSM/gPRS + RS-485"
board (for module 1), the rod for the modem, the communications terminal strip and the wiring between boards and
terminal strip.
The unit is provided with a >211 Ohm ferrite rod. The cable connecting the "AAX0001 com gSM/
gPRS + RS-485" board of the terminal (RS-485 output) must be inserted as close as possible to the
board, turning it around the centre hole twice.
The board is provided assembled on the control board and a bag (attached with a plastic tie) containing the rod cable.
connect the rod cable to the cable's rod output, and feed it out through the holes on the upper left side of the enclo-
sure. connect the end that goes outside to the rod and attach it via its magnet to the unit's enclosure.
If you obtain the "AAX0001 com gSM/gPRS + RS-485" board after having the IngecOn Sun PowerMax with
communication via serial RS-485, install the new board. To do this, the "AAP0022 com RS-485" board of the first
module must be replaced with the "AAX0001 com gSM/gPRS + RS-485" board. Observe the precautions stipulated
in section "4.3.2. Additional risks and measures in handling tasks" for Handling tasks.
Once mounted on the board, the communication RS-485 cables must be wired as they were on the other board, and
the rod must be connected as described above.
connect the rod cable to the cable's rod output, and feed it out through the holes on the upper left side of the enclo-
sure. connect the end that goes outside to the rod and attach it via its magnet to the unit's enclosure.
See "AAX2002IKI01Installation guide for communications Devices".

5.4.9. connection for ethernet communication

At the request of the installer, inverters may optionally incorporate hardware for communicating via ethernet. This
hardware comprises one to three "AAP0022 com RS-485" boards (one per module except for module 1) that are
supplied mounted on the control board in each power block, a "AAX0004 com ethernet + RS-485" board (for module
1), the communications terminal strip and the wiring between boards and terminal strip.
The unit is provided with a >211 Ohm ferrite rod. The cable connecting the "AAX0004 com ethernet
+ RS-485" board of the terminal (RS-485 output) must be inserted as close as possible to the board,
turning it around the centre hole twice.
The board is provided assembled on the control board and a bag (attached with a plastic tie) containing the ethernet
cable. connect the cable to the board's ethernet output and feed it out through the holes on the upper left side of
the enclosure.
If you obtain the "AAX0004 com ethernet + RS-485" board after having the IngecOn Sun PowerMax with
52
Installation manual
AAV2000IKI01