5.4.14. Ac intake neutral connection

The Ac output connection is configured as an IT network. Voltage sensing and balancing may be improved y connecting
the IT network neutral.
The neutral is used only for measuring the intake voltage and no power flows through it.
This neutral must never be connected to ground.
INGECoN SUN PowerMax
each power module has an individual neutral connection.
If the transformer neutral is distributed, each module must be connected. The connection cable must be no greater
than 2.5 mm
.
2
Ingeteam recommends the connection of the neutral of the voltage intake. This connection is required
by some regulations. consult the Ingeteam technical department.
56
Connecting neutral to the inverter
Auxiliary protections