Installation Drawings; Figure 47 Ups Dimensions- Front View; Figure 48 Lineup Arrangement, Liebert Apm With Battery And Liebert Bdcs - Emerson Liebert APM 15-90kVA Manual

50/60hz
Table of Contents

Advertisement

7.0
I
NSTALLATION
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert
APM UPS System cabinets (UPS, Liebert BDC and battery).

Figure 47 UPS dimensions- front view

55.4" (1408mm)
23.8" (604mm)
Battery
Cabinet #1
FRONT VIEW

Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs

®
Liebert
APM
D
RAWINGS
78.7"
(2000mm)
UPS
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4.Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national
and local electrical codes.
9. All battery cabinets must be positioned on the
left side of the UPS.
Total Width with Additional Battery Cabinets
Number of
Battery Cabinets
2
3
4
UAM03000
Rev. 0
UAM03001
Rev. 1
62

Installation Drawings

Total Width
In. (mm)
79.1 (2008)
102.7 (2608)
126.3 (3208)

Advertisement

Table of Contents
loading

Table of Contents