Matching Battery Cabinets—Optional
Although the individual battery cells are sealed (valve-regulated) and require only minimal
maintenance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks
should be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS
operating, measure and record battery float voltage. With the DC circuit breaker open, measure and
record the nominal (open circuit) voltage. Both these measurements should be made across the final
positive and negative terminal lugs. Compare these values with those shown below. The recorded
nominal voltage should be no less than the value shown; while the recorded float voltage should be
within the range shown. If a discrepancy is found, contact Liebert Services.
Table 1
Battery voltage, nominal and float
Battery Voltage, VDC
Nominal/
Number of Cells
Open Cell
144
288
Power Connections: Check for corrosion and connection integrity. Inspect wiring for discolored or
cracked insulation. Clean and/or retighten as required. Refer to torque specifications in Table 2.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and
tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more
than the retorque value. Table 2 shows battery retorque values.
Table 2
Battery retorque values
Battery Mfr.
Battery Model #
HX205-FR
HX300-FR
HX330-FR
HX400-FR
Enersys
HX500-FR
HX540-FR
16HX800F
16HX925F
If the system uses a different model battery, contact Liebert Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once
disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.
The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and
insulate the cables connected to the battery. Secure each battery shelf with retaining screws when
maintenance is complete.
Other DC Sources
If the UPS system uses a DC source other than a factory-supplied Matching Battery Cabinet, perform
maintenance on the DC source as recommended in the DC source manufacturer's maintenance
manual, available on the manufacturer's Web site.
Float
324
Retorque Value
65 in-lb