Figure 49 UPS dimensions continued, center of gravity—side, top and bottom views
9.2"
(235mm)
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
0.8"
TOP VIEW
(21mm)
39-1/2"
(1000mm)
Front
LEFT SIDE VIEW
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit and 12" (305)
rear clearance required for air exhaust and 36" (914)
front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate
conduits.
7. Only copper cables are recommended.
Refer to Tables 11 and 13 for Dimensions X, Y and Z in each Liebert APM model.
3"
(77mm)
28.3"
(719mm)
Bracket
Centers
34.3"
(871mm)
BOTTOM VIEW
31.5" (800mm)
without Side Panels
Center of
Gravity
78.7"
(2000mm)
Dimension
Y; See Pg. 2
1.56"
(40mm)
Dimension
See Pg. 2
X
OVERALL
FRONT VIEW
23.4"
(595mm)
See Detail A
Power
Cable Entry
21.26 x 7.87"
(540 x 200mm)
Vent Screen
Caster
8.9"
(226mm)
28.3"
(719mm)
1.4"
(36mm)
Vent Screen
Front and Back
Display
31.8"
(808mm)
8. All wiring is to be in accordance with national and local
electrical codes.
9. See page 2 of 5 drawing: UAM02010B for weight table
and centers of gravity for UPS at 208V.
10. See page 3 of 5 drawing: UAM02010C for weight table
and centers of gravity for UPS at 480V.
11. See page 4 of 5 drawing:UAM02010D for weight table and
centers of gravity for UPS at 600V.
12. See page 5 of 5 drawing:UAM02010E for weight table and
centers of gravity for UPS with internal maintenance bypass.
63
Installation Drawings
Mechanical
Stop
Detail A
Center of
Gravity
Front
Dimension
Z
RIGHT SIDE VIEW
UAM2010A
Rev. 2
See
Page 2
®