9.2

Mimic Display Indicators

Figure 69 Mimic display indicators location

Mimic indicators
Mimic indicators
1. Rectifier indicator
1. Rectifier indicator
2. Battery indicator
2. Battery indicator
3. Bypass indicator
3. Bypass indicator
4. Inverter indicator
4. Inverter indicator
5. Load indicator
5. Load indicator
6. Status indicator
6. Status indicator
Mimic indicators show the operational status of the Liebert APM by their color—green, amber or
red—and whether they are ON (solid), flashing or OFF. Table 23 provides a guide to interpreting the
various states of the indicators.
Table 23
Mimic display status indicators
Indicator
(see Figure 69)
Green
1. Rectifier
Load on Rectifier
Battery Powering
2. Battery
the Load
Load on Bypass
3. Bypass
Power
Inverter Powering
4. Inverter
the Load Normally
5. Load
UPS output On
No Alarms—UPS
6. Status
Working Normally
* Battery or battery converter abnormal events include these event messages (see Table 57): No Battery, Battery Replaced, Battery
Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.
®
Liebert
APM
Flashing Green / Amber
Flashing Green: Utility normal,
but rectifier not operating
Flashing Green: Battery
pre-warning (low battery)
Flashing Green: Inverter on
standby
Amber: UPS has a general
alarm
86
Operator Control and Display Panel
E ME R S O N
3
TM
Network Power
4
5
2
6
STATUS
1
Red
Rectifier fault
Battery or battery
converter abnormal*
Bypass out of
normal range
Inverter fault
UPS output overloaded
UPS has a serious alarm
Off
Rectifier is normal, but utility
is abnormal
Battery and converter are
normal, and battery is not
discharging
Bypass Normal
Inverter normal but Off
UPS has no output power