Ups Electrical Characteristics; Table 41 Ups Currents And Terminals-Input (For Single-Input Unit, 208V Operation); Table 42 Ups Currents And Terminals-Input (For Dual-Input Unit Only, 208V Operation); Table 43 Ups Currents And Terminals-Bypass Input (For Dual-Input Units, 208V Operation) - Emerson Liebert APM 15-90kVA Manual

50/60hz
Table of Contents

Advertisement

11.4

UPS Electrical Characteristics

Refer to additional circuit breaker notes in 3.2.8 - Accessory Fuses and Backfeed Breaker
Wiring.
NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect
breaker must be provided for AC input, DC input and AC output. Recommended cable sizes are
suitable for operation at a maximum temperature of 86°F (30°C). For continuous operation at
temperatures above 86°F (30°C), the site design should include cables that meet requirements
for 104°F (40°C) installations.
Table 41
UPS currents and terminals—Input (for single-input unit, 208V operation)
Nominal
Maximum
Unit
Input
Rating
Current
Current
15
45
30
90
45
134
60
179
75
224
90
268
Table 42
UPS currents and terminals—Input (for dual-input unit only, 208V operation)
Nominal
Maximum
Unit
Input
Rating
Current
Current
15
45
30
90
45
134
60
179
75
224
90
268
Table 43
UPS currents and terminals—Bypass input (for dual-input units, 208V operation)
Nominal
Unit
Input
OCP Device
Rating
Current
15
42
30
84
45
126
60
168
75
210
90
252
®
Liebert
APM
OCP
Input
Device
Rating
Bolt Size
56
70
M10 (3/8")
112
125
M10 (3/8")
167
200
M10 (3/8")
223
250
M10 (3/8")
279
350
M10 (3/8")
334
400
M10 (3/8")
OCP
Input
Device
Rating
Bolt Size
56
70
M10 (3/8")
112
125
M10 (3/8")
167
200
M10 (3/8")
223
250
M10 (3/8")
279
350
M10 (3/8")
334
400
M10 (3/8")
Rating
Bolt Size
60
M10 (3/8")
110
M10 (3/8")
175
M10 (3/8")
225
M10 (3/8")
300
M10 (3/8")
350
M10 (3/8")
Maximum Recommended Lug (T&B)
75°C Wire
Current, tot
Wire
130
(1) #1
150
(1) 1/0
200
(1) 3/0
300
(2) 1/0
350
(2) 2/0
460
(2) 4/0
Maximum Recommended Lug (T&B)
75°C Wire
Current, tot
Wire
130
(1) #1
150
(1) 1/0
200
(1) 3/0
300
(2) 1/0
350
(2) 2/0
460
(2) 4/0
75°C Wire
Current, tot
Wire
130
(1) #1
150
(1) 1/0
175
(1) 2/0
230
(1) 4/0
300
(2) 1/0
350
(2) 2/0
118
Specifications and Technical Data
Compression
Mechanical
Lug Two Hole
Lug Two Hole
3/8" Bolt
54857BE
54860BE
54864BE
54860BE
54862BE
54866BE
Compression
Mechanical
Lug Two Hole
Lug Two Hole
3/8" Bolt
54857BE
54860BE
54864BE
54860BE
54862BE
54866BE
Maximum Recommended Lug (T&B)
Compression
Mechanical
Lug Two Hole
Lug Two Hole
3/8" Bolt
3/8" Bolt
54857BE
54860BE
54862BE
54866BE
54860BE
54862BE
3/8" Bolt
32209
32209
32211
32209
32209
32211
3/8" Bolt
32209
32209
32211
32209
32209
32211
32209
32209
32209
32211
32209
32209

Advertisement