7. CHIMNEY AND DRAFT
This furnace must be connected to a chimney certified for use with wood burning heating appliances. A 6 chimney and
flue pipe are mandatory for the Mini-Caddy.
The unit is not to be connected to a chimney serving another appliance. If the flue pipe draft exceeds -0.06 IN.W.C., a
barometric damper should be installed. Never install a manual damper. The barometric damper must be adjusted so
that the maximum draft measured in the flue pipe does not exceed -0.06 IN.W.C. Please note that a draft exceeding
-0.06 IN.W.C. could produce an uncontrollable fire. On the other hand, the minimum draft required is 0.04 IN.W.C.
in the flue pipe on the wood side, no matter what type of furnace (WOOD or WOOD / ELECTRIC). The air inlets
should in no case be modified to increase combustion.
8. SAFETY RULES
THE INFORMATION GIVEN ON THE CERTIFICATION LABEL AFFIXED TO THE APPLIANCE ALWAYS
OVERRIDES THE INFORMATION PUBLISHED, IN ANY OTHER MEDIA (OWNER'S MANUAL, CATALOGUES,
FLYERS, MAGAZINES AND/OR WEB SITES).
8.1. GENERAL REQUIREMENTS
MAKE SURE THE HEAT EXCHANGERS, THE FLUE PIPES AND THE CHIMNEY ARE CLEAN AND IN GOOD
CONDITION.
DO NOT USE CHEMICAL PRODUCTS OR LIQUIDS TO LIGHT THE FIRE.
DO NOT BURN WOOD COATED WITH PAINT, GLUE OR CHEMICAL PRODUCTS.
DO NOT BURN WASTES OR FLAMMABLE LIQUIDS SUCH AS GASOLINE, NAPHTHA, MOTOR OIL, OR OTHER
UNSUITABLE MATTERS.
DO NOT STORE WOOD IN THE VICINITY OF THE FURNACE. RESPECT THE REQUIRED CLEARANCES
BETWEEN COMBUSTIBLE MATERIALS AND THE SOURCE OF HEAT.