9.8. FLUE AND BAROMETRIC DRAFT CONTROL CONNECTION

The flue outlet on the Mini-Caddy furnace is 6" in diameter and the wood only or wood/electric models may be installed
with a 6" chimney approved for use with wood burning heating appliances (2100°F). If the draft exceeds -0.06 IN.W.C.,
a barometric damper must be installed. Never install a manual damper. Secure the flue collar to the flue adapter with
three screws.
For a proper installation, follow the advice below:
All the flue pipe joints must be secured with three screws.
Make sure that each screw goes through the inner wall of both connectors (male and female). See pictures below
showing a male-female coupling.
A minimum rise of ¼" per horizontal foot must be respected.
PROPER INSTALLATION
FLUE
ADAPTER
WOOD ONLY
Diameter 6"
IMPROPER INSTALLATION
CAUSES
RESTRICTION