BLOWER
DISTRIBUTION
The fuse of the distribution fan is blown: Change the 12A fuse on the power board.
The pressure in the plenum is too high: Make sure your air distribution system is well balanced and that the filter is not
dirty or clogged. Ensure that returns / side vents are not blocked.
14.2.2. NO HEAT
This message appears:
When the wood furnace failed to raise the temperature in the plenum enough to reach the KIP or
When the temperature does not reach 100 F in the plenum in less than five minutes for auxiliary heat.
Make sure there is a fire in the furnace or the auxiliary heating sources are functional and well connected.
14.2.3. COMMUNICATION ERROR
Communication error: The information from the touch screen cannot be read by the link board. It is possible that the
telecommunication wire is not plugged in. Make sure each end of the wire makes good contact in the connector. It is
also possible that the wire is damaged. In this case, replace it.
14.2.4. SMOKE SMELL
Worn gaskets. Gaskets may be allowing smoke spillage (doors, clean out traps, etc). Make sure that all gaskets
are in good condition and replace them with original parts if necessary. Make sure all doors are well adjusted.
Negative pressure. A faint wood-burning odor during ignition or shut down is normal. Although, if this increases
beyond what is considered normal or if you notice an unusual soot build-up on walls or furniture, check your
chimney system carefully for leaks and make sure all gaskets are in good condition.
14.2.5. THE TOUCH SCREEN DOES NOT LIGHTUP.
There is no electrical current going to the furnace. Check if the furnace is connected and if there is current in
the wall outlet. Check if the fuse is blown. Replace it if necessary.
. Replace it if necessary.