Hot Air Plenum; Parallel Installation - CADDY PF01302 Installation And Operating Instructions Manual

Table of Contents

Advertisement

NOTE:
It is recommended to install an outside air inlet with a diameter of at least 4" in the room where the heating appliance is
installed (see drawing below). It is preferable to choose a wall which is not exposed to dominant winds, depending on
the conditions surrounding your house.
N.B. The owner of the furnace is responsible for the room's air quality in case of negative pressure or
temporary negative pressure.
If there is a fan in the wood storage room, make sure it does not create a depression in the room where the furnace is
installed.

9.12. HOT AIR PLENUM

Plenums installed on the furnace must be made of metal in accordance with NFPA 90B, 2-1.3.
The hot air plenum coming out of the furnace is to have a minimum height of 24" (610 mm) if the top of the first vertical
section is not flush with the first horizontal section. Otherwise, the minimum height is 18" (457mm). These dimensions
for all hot air furnaces are in accordance with the standards CSA B140.4 et UL 391.
NOTE: TO ENSURE ADEQUATE STATIC PRESSURE, THE SYSTEM SHOULD BE BUILT IN A WAY THAT THE
VOLUME OF COLD AIR RETURN IS AT LEAST EQUAL OR SLIGHTLY HIGHER THAN THE VOLUME OF THE HOT
AIR DISTRIBUTION.

9.13. PARALLEL INSTALLATION

The installation of the Mini-Caddy with another furnace using the same ductwork is not allowed in Canada. This type
of installation is only allowed in the United States. Ideally, the maximum BTU input of the existing oil, gas, or
electric furnace should be equal or higher than the maximum BTU input of the wood furnace. It is mandatory to
respect minimum clearances between the ductwork and combustible material as if the wood furnace was installed as a
standalone unit. The ductwork and furnace should be adjusted in order to reach a static pressure of at least 0.20
IN.WC, but not more than 0.50 IN.WC. A back-flow damper should be installed in the plenum. The back-flow damper
assures that when either unit is operated by itself, the hot air will flow into the home, and not back through the other
furnace. Depending on your installation (see figures examples below), a back-flow damper may be required in each
plenum.
Free air entry
Exterior wall
Insulated pipe (full length)
Fresh air
intake
18"
457mm
MIN.
25

Advertisement

Table of Contents
loading

Table of Contents