Omron C200HW-CLK21 Operation Manual page 64

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Message Service Procedure
6. Set the data link mode.
Contents
Enable 62 nodes for a
wired network.
Note When using fewer than 33 nodes, make sure that the Wired Network
62 Node Enable Bit in the DM Parameter Area software switches is
turned OFF to restrict the network to 32 nodes maximum. To con-
struct a network containing more than 32 nodes, all nodes must use
the CS1W-CLK21-V1 or CJ1W-CLK21-V1.
7. Create the user program.
Contents
a. Prepare the send and receive
data in memory.
b. Prepare the control data for the
communications instruction.
c. Check the conditions for exe-
cuting the SEND/RECV or
CMND instruction.
d. Execute the SEND/RECV or
CMND instruction.
e. Execute other instructions are
required for the results of the
communications instruction,
(e.g., retry or error processing
if an error occurs).
Method
Use Support Software
All nodes
for the PLC or a Pro-
This setting must be
gramming Console.
made when construct-
ing a network that
uses a node address
higher than 32 (See
note.)
Remarks
Stored in the memory areas of the
source node
The standard input conditions are
the Active Node Flags for the
source and destination nodes, and
the Port Enabled Flag.
---
The standard input condition is the
Port Error Flags.
C200HX/HG/HE PLCs have 1
communications port for each
operating level. When 2 or more
communications instructions are
executed at the same time, exclu-
sive control is necessary.
CS-series, CJ-series, CVM1, and
CV-series PLCs have 8 communi-
cations ports. When 9 or more
communications instructions are
executed at the same time, exclu-
sive control is necessary.
CQM1H-series PLCs have only 1
communications port. When 2 or
more communications instructions
are executed at the same time,
exclusive control is necessary.
Section 2-2
Nodes
Page
78
Page
166
189
41