Omron C200HW-CLK21 Operation Manual page 68

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Component Names and Functions
Wired Unit Indicators
Name
Color
RUN
Green
(operating)
ERC (communica-
Red
tions error)
ERH
Red
(PLC error)
INS
Yellow
(network participa-
tion)
SD
Yellow
(send)
RD
Yellow
(receive)
M/A
Yellow
(data link mode)
LNK
Yellow
(data link)
TER
Yellow
(terminating resis-
tance)
Note Even when the local node does not participate in the data link, the
indicator will be lit if there are manually set data links active on the
network.
For details refer to 9-1 Troubleshooting Using Indicators .
Status
Lit
Unit operating normally.
Not lit
Unit error.
Lit
Communications error, node address
setting error (same address set twice), or
hardware error.
Not lit
Normal operation
Lit
PLC error, PLC interface error, EEPROM
error, unit number error, or I/O table not
set
Not lit
No error.
Lit
Unit is participating (inserted) in the net-
work.
Not lit
Unit is not participating (inserted) in the
network.
Lit
Data transmission.
Not lit
No data transmission.
Lit
Data reception.
Not lit
No data reception.
Lit
Manual
(see note)
Not lit
Automatic
Lit
Data links participating.
Flashing
Error in data link table.
Not lit
Not in a data link or data link inactive.
Lit
Terminating resistance switch ON.
Not lit
Terminating resistance switch OFF.
Section 3-1
Meaning
Note:
M/A is always not lit
when data links are not
active in the network.
45