Omron C200HW-CLK21 Operation Manual page 255

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Response Codes
Main code
26: Command error
30: Access right error
40: Abort
232
Sub-
Probable cause
code
01
The specified area is not protected.
This response code will be returned if
an attempt is made to clear protection
on an area that is not protected.
02
An incorrect password has been speci-
fied.
04
The specified area is protected.
To many commands at destination.
05
The service is being executed.
06
The service is not being executed.
07
Service cannot be executed from local
node because the local node is not part
of the data links.
A buffer error has prevented returning a
normal response.
08
Service cannot be executed because
necessary settings haven't been made.
09
Service cannot be executed because
necessary settings haven't been made
in the command data.
0A
The specified action or transition num-
ber has already been registered.
0B
Cannot clear error because the cause
of the error still exists.
01
The access right is held by another
node.
(Either a Programming Device at the
other node is executing an SFC online
edit, or the other node is executing an
ACCESS RIGHT ACQUIRE or
ACCESS RIGHT FORCED ACQUIRE
command.)
01
Command was aborted with ABORT
command.
Remedy
The program area is not protected, so it isn't
necessary to clear protection.
Specify a password that is registered.
Execute the command again after executing
the PROGRAM AREA PROTECT CLEAR
command for the PLC.
The destination has received more than 5
commands. Either interrupt servicing or wait
for servicing to complete before re-execut-
ing the command.
Execute the command again after the ser-
vice has been completed or aborted.
Execute the service if necessary.
Execute the service from a node that is part
of the data links.
Reset the board. If the error persists,
replace the board.
Make the necessary settings.
Check the command format of and make
the necessary settings.
Execute the command again using an
action or transition number that hasn't been
registered.
Eliminate the cause of the error and exe-
cute the ERROR CLEAR command.
Execute the command again after the
access right has been released.
(The command can be executed after the
ACCESS RIGHT FORCED ACQUIRE or
ACCESS RIGHT RELEASE command is
completed. Releasing the access right
might affect processes in progress at the
node that held the access right.)
---
Section 6-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents