Memory Areas
DM Area: CS/CJ CPU Bus Unit Area
The CS/CJ CPU Bus Unit Area (DM Area) is allocated to CS/CJ CPU Bus Units according to the unit numbers
assigned to them, as shown below. Each Unit is allocated 100 words, of which 10 words are used. In the Con-
troller Link Unit this area is called the DM Area.
Software Switches (DM30000 + 100
15 14 13 12 11 10 9
0
0
0
0
Data link status
storage format
0: 8-bit format
1: 4-bit format
Wired Network 62 Node
Enable Bit
0: 32 nodes max.
1: 62 nodes max.
CS1 CPU Bus Unit PLC Setup Initialization (See note 1.)
0: Do not initialize CS1 CPU Bus Unit PLC Setup
1: Initialize CS1 CPU Bus Unit PLC Setup
Polling node/polled node bit
0: Polling node
1: Polled node
Note 1: Initializes the network parameters registered in the CS1 CPU Bus Unit PLC Setup Area on the CPU Unit
and clears the data link tables.
2: Be sure to set the bit in the DM Area's (CPU Bus Unit Area's) software switches (D30000 + 100
number) described as "always set to 0" to 0. Not doing so may result in the data link not starting properly.
If a data link is started with bit 7 of the software switches set to 1, the data link status will be stored in a
format different to the one described in this manual (when using CS-series or CJ-series Controller Link Units).
Unit no.
0
1
2
3
4
5
6
7
Unit No.) (See pages 145, 243, 249, 318.)
8
7
6
5
4
3
2
1
0
0
0
0
Data link mode
000: Manual
001: Automatic, equality layout
101: Automatic, 1:N allocation
Words
Unit no.
DM30000 to
8
DM30009
DM30100 to
9
DM30109
DM30200 to
10
DM30209
DM30300 to
11
DM30309
DM30400 to
12
DM30409
DM30500 to
13
DM30509
DM30600 to
14
DM30609
DM30700 to
15
DM30709
0
0: Always set to 0.
Data Link Start Bit
Start: Changed from OFF to ON or set to ON
when power is turned ON.
Stop: Changed from ON to OFF.
Appendix B
Words
DM30800 to
DM30809
DM30900 to
DM30909
DM31000 to
DM31009
DM31100 to
DM31109
DM31200 to
DM31209
DM31300 to
DM31309
DM31400 to
DM31409
DM31500 to
DM31509
unit