Occurs Again, Replace The - Omron C200HW-CLK21 Operation Manual

Controller link units
Hide thumbs Also See for C200HW-CLK21:
Table of Contents

Advertisement

Status Area and Troubleshooting
Other Status
Bit status
Duplicate Operating Lev-
els/Refresh Error:
Operating level 0: AR0011
Operating level 1: AR0010
One of the above flags is 1:
ON
Routing Table Error/Unit
Restart:
Operating level 0: AR0113
Operating level 1: AR0112
One of the above flags is 1:
ON
Communications controller
hardware error:
Operating level 0: AR1114
Operating level 1: AR1514
One of the above flags is 1:
ON
EEPROM error:
Operating level 0: AR1115
Operating level 1: AR1515
One of the above flags is 1:
ON
Inconsistent network
parameters:
Operating level 0: AR2407
Operating level 1: AR2406
One of the above flags is 1:
ON
Probable cause
The same operating level is
set twice within the same
PLC.
A refresh error has
occurred between the PLC
and the Unit.
The routing table data
within the DM Area is dam-
aged.
There is an error in the
routing table setting or a
Routing Table Enable Bit
(software switch) setting
error.
The Controller Link Unit is
faulty.
An error occurred when
writing data to EEPROM.
The EEPROM data link
tables or the network
parameters are damaged.
There is an error in the
data link or network param-
eter settings.
Indicates that the network
parameters in the
EEPROM of the Controller
Link Unit differ from those
in the Network.
Section 9-2
Probable remedy
If two units are required,
set them to different oper-
ating levels.
Secure the Controller Link
Unit firmly.
For C200HX/HG/HE PLCs,
tighten the screws on the
Bus Connection Unit.
If the error occurs even
when the Unit is mounted
on another PLC, replace
the Controller Link Unit.
Refer to 7-4 Setting Rout-
ing Tables and reset cor-
rectly. If the error occurs
again, replace the Control-
ler Link Unit.
When using routing tables
refer to 7-4 Setting Routing
Tables and reset them cor-
rectly.
When no routing tables are
being used, turn OFF the
Routing Table Enable Flag.
Replace the Controller Link
Unit.
Remake and set the data
link table and the network
parameters. If the error

occurs again, replace the

Controller Link Unit.
Check the network param-
eters on the Network,
using the Controller Link
Support Software, and
reset the necessary
parameters.
303

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents