Tap Restore Defaults. A warning is displayed. Tap Yes. Except for current setting parameters
mentioned above, other parameters are restored to the preset values. Perform this operation
with caution.

5.12 Teamwork Settings

Teamwork control is a solution for allocating the overall cooling and humidification capacity
of the data center, improving the usage efficiency of the precision air conditioners by
preventing random operation. Multiple NetCol5000-Cs are interconnected and controlled in a
central control mode. In this manner, the teamwork function and rotation of the master and
slave NetCol5000-Cs can be implemented. A maximum of 32 NetCol5000-C can be
interconnected using the CAN bus bar. The device with the teamwork address as 1 is the
master one, which collects, processes, and delivers data.
Teamwork setting home page
After the teamwork is set successfully, the teamwork home page will be displayed as shown
in
Figure
Figure 5-39 Teamwork topology
Table 5-2 Note for the page
No.
1
2
Issue 02 (2013-12-10)
5-39.
Parameters
ON/OFF/NA
01/02/03...
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Note
ON indicates the NetCol5000-C is started and OFF
indicates the opposite. NA indicates the
NetCol5000-C is off-line.
Indicates the device address. 01 is the master one
and the rest are all slave ones.
5 Controller Operate Guide
81