Item
Fan speed characteristic
Total airflow
Maximum operating
pressure
Air filter
Condensate pump
Dimensions
(W x D x H)
Packing dimensions
(W x D x H)
Net weight/Gross
weight
Pipe and cable routing
Environmental
certification

2.8 Performance Curves

Cooling Capacity and Water Supply
With rated power and maximum air volume, the NetCol5000-C has different performance
specifications for cooling capacity, sensitive heat, and water supply based on chilled water
temperatures and temperature rises.
list the performance specifications.
Table 2-4 Specifications for a 5.5° C chilled water supply system
Item
Return air
temperature
5° C
temperature
Issue 02 (2013-12-10)
1: The return air dry-bulb temperature / wet-bulb temperature is 37.8 ° C/ 20.8 ° C, the temperature of
chilled water is 10 ° C and flow is 5.04 m
Dry-bulb
temperature (° C)
Wet-bulb
temperature (° C)
Cooling capacity
(kW)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Description
Stepless speed adjustment
3
5100 m
/h
1.6 MPa
G3 filter
Yes
300 mm × 1000 mm × 2000 mm
300 mm × 1200 mm × 2000 mm
760 mm × 1350 mm × 2200 mm
240 kg/250 kg
Installed on a concrete floor or an ESD floor
RoHS, WEEE and REACH
3
/h.
Table
2-4,
Table
Performance Specifications
40
37
21.4
20.5
40.63
36.79
2 Product Description
2-5,
Table
2-6,
Table
2-7, and
35
32
19.8
18.9
33.21
29.27
Table 2-8
28
17.6
23.98
11