Troubleshooting - Huawei NetCol5000-C User Manual

Chilled water-cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-C:
Table of Contents

Advertisement

NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual
Alarm
Alarm Name
ID

6.4 Troubleshooting

Table 6-6
Table 6-6 Common faults of NetCol5000-C and handling methods
Symptom
The fan does not rotate
after the NetCol5000-C
starts.
The humidity and
temperature sensor
cannot detect the
humidity and
temperature.
The fan generates loud
noises.
The NetCol5000-C
leaks.
A NetCol5000-C is
Issue 02 (2013-12-10)
System
Severity
Operation
describes the common faults of NetCol5000-C and handling methods.
Possible Causes
The power supply module of the
fan is faulty or abnormal
(including the fuse of the power
supply module is blown.)
The fan fuse is blown.
Cables to the fan are faulty.
Parameter settings on the
controller are incorrect.
DIP switches of the humidity and
temperature sensor are incorrectly
set.
The humidity and temperature
sensor is faulty.
The air filter is blocked.
Dirt exists at the fan air exhaust
vent.
The fan is not securely installed.
The fan is faulty.
The thermal insulation tube of the
NetCol5000-C is damaged.
The condensate drainpipe is
blocked.
The pipes leak.
The jumper cap of the chilled
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Possible Causes
Troubleshooting
Ensure that the power supply module
of the fan is inserted to the subrack. If
the fault persists, replace the power
supply module (or replace the fuse).
Replace the fan fuse.
Check whether the cables to the fan
short-circuit or are disconnected.
Check that the humidity and
temperature sensor is enabled on the
controller.
Check that DIP switches of the
humidity and temperature sensor map
the corresponding aisle.
If the fault persists after the preceding
operations, replace the humidity and
temperature sensor.
Clean the air filter.
Clear the fan air exhaust vent.
Fasten the fan screws
Replace the fan.
Check whether thermal insulation tube
of the NetCol5000-C is securely
installed and repair the damaged
thermal insulation tube.
Ensure that the drainpipes are not bent
by a large angle, the drainpipe
connectors are securely installed, the
condensate pump is not faulty, and the
floats are not faulty.
Check the pipes and weld the pipe or
fasten related bolts if the pipes leak.
Check the W1 jumper of the chilled
Recovery Measures
sensor.
114