6.5.9 Replacing a Water Inlet or Outlet Temperature Sensor

Prerequisites
Context
Recommended tools: needle-nose pliers.
Preparation: maintain from the rear door.
Procedure
Step 1 Remove the rear door and air filters.
Step 2 Cut the heat insulation cotton wrapped around the pipes.
Step 3 Use a needle-nose pliers to clip out spring tongues fastening the temperature sensor and
remove the water inlet or outlet temperature sensor, as shown in
Step 4 Remove the waterproof plug of the temperature sensor probe, insert the spring tongues of the
temperature sensor to the sleeve and then insert the temperature sensor probe into the sleeve.
Step 5 Wrap the temperature sensor pipes with insulation cotton.
Step 6 Install the air filters and rear door.
Figure 6-9 Replacing the water inlet or outlet temperature sensor
----End
Issue 02 (2013-12-10)
The water inlet or outlet temperature sensor needs to be replaced.