Replacing A Condensate Pump - Huawei NetCol5000-C User Manual

Chilled water-cooled in-row precision air conditioner
Hide thumbs Also See for NetCol5000-C:
Table of Contents

Advertisement

NetCol5000-C Chilled Water-Cooled In-Row Precision
Air Conditioner
User Manual

6.5.4 Replacing a Condensate Pump

The condensate pump stops drain water.
Prerequisites
Context
Recommended tool: Phillips screwdriver
Preparations: maintain from the rear door, and power off the condensate pump.
Procedure
Step 1 Remove the rear door and air filters.
Step 2 Disconnect all circuit breakers.
Step 3 Remove bolts on the condensate pump using a Phillips screwdriver, as shown in
Step 4 Remove the condensate drainpipes and control cables.
Step 5 Remove the screws fastening the condensate pump using a Phillips screwdriver and remove
the condensate pump, as shown in
Step 6 Install a new condensate pump.
Step 7 Install the rear door and air filters.
Step 8 Tap Maint > Performance Maint on the home screen to enter the performance maintenance
screen, and clear accumulated running time of the condensate pump.
Issue 02 (2013-12-10)
The condensate pump needs to be replaced.
A spare and functional condensate pump valve is available.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 System Operation and Maintenance
Figure 6-4
Figure
6-3.
118