Ceiling Concealed (Middle Static Pressure Type) - Mitsubishi Electric PURY-WP-YJM-A Data Book

Table of Contents

Advertisement

1. SPECIFICATIONS
1. SPECIFICATIONS
I.Ceiling concealed (Middle static pressure type)
Model
Power source
Cooling capacity
(Nominal)
*2 Power input
*2 Current input
Heating capacity
(Nominal)
*2 Power input
*2 Current input
External finish
External dimension HxWxD
Net weight
Heat exchanger
Water Volume
FAN
Type x Quantity
*4 External static press.
Motor Type
Motor output
Driving mechanism
Air flow rate
Sound pressure level (measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit/HBC controller
Diameter of water pipe
Inlet
*5 *6 Outlet
Field drain pipe size
Drawing
External
Wiring
Refrigerant cycle
Standard attachment
Document
Accessory
Optional parts
Filter box
Remarks
Notes :
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°CD.B./66°CW.B.), Outdoor: 35°CD.B. (95°CD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°CD.B.), Outdoor: 7°CD.B./6°CW.B. (45°CD.B./43°CW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Group units that operate on 1 branch.
PEFY-WP20VMA-E
1-phase 220-230-240 V 50/
60 Hz
*1 kW
2.2
*1 kcal/h
1,900
*1 BTU/h
7,500
kW
0.07
A
0.55
*3 kW
2.5
*3 kcal/h
2,200
*3 BTU/h
8,500
kW
0.05
A
0.44
Galvanized steel plate
mm
250 x 700 x 732
in.
9-7/8 x 27-9/16 x 28-7/8
kg (lbs)
21 (47)
Cross fin (Aluminum fin and
copper tube)
L
0.7
Sirocco fan x 1
<35> - 50 - <70> - <100> -
Pa
<150>
<3.6> - 5.1 - <7.1> - <10.2> -
mmH
O
2
<15.3>
DC motor
kW
0.085
Direct-driven by motor
(Low-Mid-High)
3
m
/min
7.5 - 9.0 - 10.5
L/s
125 - 150 - 175
cfm
265 - 318 - 371
(Low-Mid-High)
*2 dB <A>
23-26-29
EPS, Polyethylene foam,
Urethane foam
PP honeycomb fabric.
Fuse
-
HYBRID CITY MULTI/CMB-
WP-V-G
in.
Rc 3/4 screw
in.
Rc 3/4 screw
mm (in.)
O.D.32 (1-1/4)
KD94L918X01
KD94L919X01
-
Installation Manual, Instruc-
tion Book
Insulation pipe for water pipe,
Washer, Drain hose, Tie
band
PAC-KE91TB-E
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
INDOOR UNITS
PEFY-WP25VMA-E
PEFY-WP32VMA-E
1-phase 220-230-240 V 50/
1-phase 220-230-240 V 50/
60 Hz
60 Hz
2.8
2,400
3,100
9,600
12,300
0.09
0.64
3.2
2,800
3,400
10,900
13,600
0.07
0.53
Galvanized steel plate
Galvanized steel plate
250 x 900 x 732
250 x 900 x 732
9-7/8 x 35-7/16 x 28-7/8
9-7/8 x 35-7/16 x 28-7/8
26 (58)
26 (58)
Cross fin (Aluminum fin and
Cross fin (Aluminum fin and
copper tube)
copper tube)
1.0
Sirocco fan x 1
Sirocco fan x 1
<35> - 50 - <70> - <100> -
<35> - 50 - <70> - <100> -
<150>
<150>
<3.6> - 5.1 - <7.1> - <10.2> -
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
<15.3>
DC motor
DC motor
0.085
0.085
Direct-driven by motor
Direct-driven by motor
(Low-Mid-High)
(Low-Mid-High)
10.0 - 12.0 - 14.0
12.0 - 14.5 - 17.0
167 - 200 - 233
200 - 242 - 283
353 - 424 - 494
424 - 512 - 600
(Low-Mid-High)
(Low-Mid-High)
23-27-30
25-29-32
EPS, Polyethylene foam,
EPS, Polyethylene foam,
Urethane foam
Urethane foam
PP honeycomb fabric.
PP honeycomb fabric.
Fuse
-
HYBRID CITY MULTI/CMB-
HYBRID CITY MULTI/CMB-
WP-V-G
WP-V-G
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
O.D.32 (1-1/4)
O.D.32 (1-1/4)
KD94L918X01
KD94L918X01
KD94L919X01
KD94L919X01
-
Installation Manual, Instruc-
Installation Manual, Instruc-
tion Book
tion Book
Insulation pipe for water pipe,
Insulation pipe for water pipe,
Washer, Drain hose, Tie
Washer, Drain hose, Tie
band
PAC-KE92TB-E
PAC-KE92TB-E
PEFY-WP40VMA-E
1-phase 220-230-240 V 50/
60 Hz
3.6
4.5
3,900
15,400
0.11
0.14
0.74
1.15
4.0
5.0
4,300
17,100
0.09
0.12
0.63
1.04
Galvanized steel plate
250 x 1,100 x 732
9-7/8 x 43-5/16 x 28-7/8
31 (69)
Cross fin (Aluminum fin and
copper tube)
1.0
1.8
Sirocco fan x 2
<35> - 50 - <70> - <100> -
<150>
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
DC motor
0.121
Direct-driven by motor
(Low-Mid-High)
14.5 - 18.0 - 21.0
242 - 300 - 350
512 - 636 - 742
(Low-Mid-High)
26-29-34
EPS, Polyethylene foam,
Urethane foam
PP honeycomb fabric.
Fuse
Fuse
-
-
HYBRID CITY MULTI/CMB-
WP-V-G
Rc 3/4 screw
Rc 3/4 screw
O.D.32 (1-1/4)
KD94L918X01
KD94L919X01
-
-
Installation Manual, Instruc-
tion Book
Insulation pipe for water pipe,
Washer, Drain hose, Tie
band
band
PAC-KE93TB-E
Unit converter
kcal
=kW x 860
BTU/h =kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg / 0.4536
*Above specification data is
subject to rounding variation.