3. System remote controller
5.System configuration
PC for centralized control
(TG-2000A)
HUB
HUB
LAN
LAN
HUB
AG-150A
Note
Connect the LAN cable to the LAN connector on the PAC-YG50ECA.
Connect the PAC-YG50ECA and AG-150A via a HUB.
The maximum distance between the HUB and PAC-YG50ECA is 100 m (328 ft).
The LAN cable is field-supplied. Use a category 5 or better straight cable.
Use a switching HUB.
It is recommended that the number of devices to be connected between AG-150A and PAC-YG50ECA does not exceed four.
(Round-trip transmission delay time must not exceed four seconds. If the transmission delay time is set too long, a communication
error may occur.)
Each unit can control up to a total of 2000 indoor, LOSSNAY, and other units.
Each AG-150A unit can control up to a total of 150 indoor, LOSSNAY, and other units (when used with three
expansion controllers).
*1
24VDC
AG-150A
M-NET
Outdoor unit
HBC
PAC-YG50ECA
controller
Outdoor unit
HBC
controller
M-NET
Outdoor unit
HBC
PAC-YG50ECA
controller
M-NET
PAC-YG50ECA
LOSSNAY
unit
Each AG-150A unit can control up to a total of 50 indoor, LOSSNAY, and other units (without the use of
expansion controllers).
M-NET
HBC
Outdoor unit
controller
24VDC
PAC-SC51KUA
CONTROLLER
Do not connect directly to the Internet. When
connecting to the Internet through the AG-150A
etc., use a security device such as a VPN router.
*1
PAC-SC51KUA
M-NET
Indoor unit
ME remote
controller
M-NET
Indoor unit
ME remote
controller
M-NET
Indoor unit
ME remote
controller
M-NET
LOSSNAY
LOSSNAY
unit
unit
M-NET
Indoor unit
ME remote
controller
LAN
LAN
M-NET
24VDC
*1:Do not use M-NET terminal.
LOSSNAY
unit
LOSSNAY
unit
LOSSNAY
unit
LOSSNAY
unit
LOSSNAY
unit
3 - 43