2. M-NET control
2-4-3-10. AG-150A+PAC-YG50ECA (Expansion controller)
AG-150A can control max. 150 indoor units/ via expansion controllers.
AG-150A
PAC-YG50ECA
000
CN40
CN41
HBC controller
HUB
TB02
PC with
Browser
PAC-YG50ECA
LAN
000
CN40
CN41
PAC-YG50ECA
000
CN40
CN41
HBC controller
53
TB02
HBC controller
92
TB02
NOTE
When connecting AG-150A to PAC-YG50ECA, TB2 for power supply unit does not need to be connected to AG-150A.
*1 For wireless R/C and signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 AG-150A (Ver.1series) does not support the expansion controller (EC).
*3 When a PAR-31MAA is connected to a group, no other MA remote controllers can be connected to the same group.
*4 Only a single outdoor unit can be connected to a HYBRID CITY MULTI system.
24VDC
TB3
Power supply unit
<Two outdoor units>
(PAC-SC51KUA)
PURY
OC
TB7
51
CN40
CN41
DipSW2-1
ON
TB3
Group 1
Indoor unit
53
01
TB5
TB15
TB5
SRU
*4
*4
Wireless R/C
PURY
OC
TB7
TB7
51
CN40
CN41
CN40
DipSW2-1
ON
TB3
TB3
Group 1
Group 2
Indoor unit
01
02
TB5
TB5
101
102
ME R/C
ME R/C
Group 31
Group 32
Indoor unit
41
42
TB5
TB5
141
142
ME R/C
ME R/C
SYSTEM DESIGN
<One outdoor unit>
PURY
OS
OC
TB7
TB7
52
51
CN40
CN41
CN40
DipSW2-1
DipSW2-1
ON
ON
TB3
TB3
Group 2
02
03
TB15
TB5
TB15
MA R/C
PURY
OS
OC
TB7
52
91
CN41
CN40
CN41
DipSW2-1
DipSW2-1
ON
ON
TB3
03
TB5
TB2
Transmission Booster
PAC-SF46EPA
Interlocked
LOSSNAY
43
TB5
CN41
Group 40
42
TB2
TB3
TB5
TB15
Transmission Booster
PAC-SF46EPA
MA R/C
MA R/C
(Main)
(Sub)
Group 21
30
TB3
TB5
130
ME R/C ME R/C
Group 33
Group 34
44
45
TB5
TB5
144
145
ME R/C ME R/C
ME R/C
180
195
4 - 22