3. System remote controller
(2). Parts Purchased Separately
Prepare the following parts to install this device.
Required Part
Unit fixing screws
M4 screw
Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Power supply for this
device
A separate power supply for sensors may be required.
Power supply for
In the case of 24 VDC voltage, the capacity of the power supply for this unit can be increased so that the
sensors
power supply can be shared.
Use a sheathed vinyl cord or cable.
Power line
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
• CPEV
M-NET transmission
line
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.
Shows the size of the electric wire (copper wire) that is adapted to the terminal block of this device. Refer
to the usage and cautionary items of the sensor when performing settings. However, use a line with shielded
Signal lines
line.
(Sensor input lines)
[Parts to be Purchased Separately]
Name
Power supply unit
PAC-SC51KUA Power supply to the M-NET transmission line
[Commercially available parts]
Part
External 24 VDC
Supplies power to the AI controller.
power source
Sensor
Measures temperature and humidity.
4 (* M4: ISO metric screw thread)
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products.
Subject to regulations:
- IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
2
At least 0.75 mm
(AWG18)
1.2 mm to
1.6 mm • CVVS 1.25 mm to 2 mm (AWG 16 to 14)
* CPEV: PE insulated PVC jacketed shielded communication cable
* CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene
PVC: Polyvinyl chloride
Electric wire size ···· (1)Solid wire:
(2)Stranded wire: 0.75 mm (AWG18) - 1.25 mm (AWG16)
Model
Use
CONTROLLER
Specification
0.65 mm (AWG21) -
1.2 mm (AWG16)
Single strand: At least
Application
This is not required when power is to be
supplied from an outdoor unit.
Refer to "Power supply for this device" and "Power
supply for sensors" in "Required Part" above for the
capacity of the power supply.
Temperature sensor (PAC-SE40TSA) cannot be
connected.
0.18 mm
Remark
Remark
3 - 77