3. System remote controller
3. Interlock control
The DIDO controller (PAC-YG66DCA) has an interlock control function, which enables operation or set temperature change on the
M-NET devices such as indoor units and also enables signal output to the contacts on the DIDO controller.
Interlock control covers the units connected to the DIDO controller with M-NET system.
AG-150A/GB-50ADA must be connected to use the function.
Ask your dealer for interlock control setting. The setting requires special tool support.
Before using the interlock control, you must agree to the following.
1.This feature must not be used for disaster prevention or security purpose.
(Not designed to be used in situations that are life-threatening)
2.No functions must be added that allow the malfunctioning unit to run by defeating the safety features, such as
an external ON/OFF switch or a short-circuit.
CAUTION
3.Those settings for the function that are not supported by the interlocked units must not be made. All the
settings must be made within the specified range.
(Failure to observe these precautions may result in malfunctions and failures.)
4.Perform a test run for interlock control, and confirm the correct settings and normal operation.
5.The system must be configured in the way that integrates the operation of the interlocked fire and emergency
control systems.
Item
Number of events
Determinant condition for
interlock control
Interlock control contents
(to be output)
Other
AG-150A
(GB-50ADA)
Note: Do not use Interlock control function on both AG-150A/GB-50ADA and DIDO controller at the same time.
Content
24 events
At input contact change
1 action for 1 condition
• ON/OFF operation of indoor units
• Operation mode change of indoor units
• Temperature setting of indoor units
• Contact output to DIDO controller (*2)
Interlock control prohibition function is
enabled at emergency stop from AG-150A/
GB-50ADA
CENTRALIZED CONTROLLER AG-150A
HBC
Outdoor unit
controller
DIDO Controller
Interlock with contact output
ON/OFF
Interlock con
trol of DIDO controller (example)
CONTROLLER
1 event interlock with 1 unit
• Operation input ON/OFF
• Error input Error/Normal
Interlock control covers the units connected to
DIDO controllers with M-NET system.
(*1) Temperature setting range: 19-28ºC (Standard setting)
(*1)
(*2) DIDO controller itself or other DIDO controllers
in the same M-NET system.
Indoor unit
Operation ON/OFF
Interlock with M-NET devices
Lights
ON/OFF
Remarks
3 - 73