Advertisement

3. System remote controller
2. External input/output usage
NOTE : When using the AG-150A connected with the expansion controller, use external input/output function of the expansion controller.
(1). External signal input function
To use the external signal input, an external I/O adapter (PAC-YG10HA; sold separately) and an external power supply are required.
1). External input
Emergency stop/normal, ON/OFF and prohibit/permit of local remote controller operation can be controlled for all air
conditioners being controlled by using a voltage (12VDC or 24VDC) contact signal from an external source.
(Select with the function select setting.)
Function
No
name
Do not use external input signal
1
Not in use
(factory setting)
Execute emergency stop/normal
Emergency
with level signal
stop
2
(Level signal)
Perform ON/OFF with level signal
ON/OFF
3
(Level signal)
ON/OFF
Perform ON/OFF, prohibit/permit
prohibit/permit
with pulse signals.
4
(Pulse signal)
* DIDO controller (PAC-YG66DCA) cannot be collectively run or stopped by using the external input function. But when
[Emergency stop (Level signal)] is selected, DIDO controller (PAC-YG66DCA) can be collectively stopped by setting the
appropriate switches on the DIDO controller.
2).
Level signal and pulse signal (12VDC or 24VDC)
(A) Level signal
Contact ON
Contact OFF
Contact ON
Contact OFF
3).
External input specifications
CN5
Lead wire
No.5
Orange
No.6
Yellow
No.7
Blue
No.8
Gray
No.9
Red
(A) For level signal
When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Air conditioning units that came to an emergency stop will remain stopped after
the emergency stop is cancelled. Manually start up each unit to restore the previous operation.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.5 to 1 sec.
External signal input function
OFF
ON
OFF
Emergency stop
Normal
Normal
Emergency stop/normal level signal
Emergency stop/normal input
Not used
Not used
Not used
External DC source "+
CONTROLLER
Remarks
The local remote controller ON/OFF operations, and the
controller ON/OFF operation and prohibit/permit change
operations will be prohibited during emergency stop.
Timer operation will also be prohibited.
The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/permit change
operations will be prohibited.
Timer operation will also be prohibited.
Set the pulse width while the contact is ON to 0.5 to 1 sec.
(B) Pulse signal
(Example) for ON/OFF
Signal 1 (run)
Contact ON
Contact OFF
Signal 2 (stop)
Contact ON
Contact OFF
*The prohibit/permit input is the same.
ON/OFF, level signal
ON/OFF, prohibit/enable pulse signal
ON/OFF input
ON input
Not used
OFF input
Local remote controller operation
Not used
prohibit input
Local remote controller operation
Not used
enable input
12VDC"
or "+
24VDC"
0.5 to 1 sec
0.5 to 1 sec
OFF
ON
OFF
3 - 24