3. System remote controller
(2). Parts Purchased Separately
Prepare the following parts to install this device.
Required Part
Unit fixing screws
M4 screw
Commercially available power source: 24 VDC 10% 0.2 A (Minimum loading), SELV circuit, power line with
grounding terminal
Power supply for this
device
Power line
Use a sheathed vinyl cord or cable. At least 0.75 mm
Type of the cable: Sheathed vinyl cords or cable which comply with the following specifications or
equivalent.
• CPEV 1.2 mm to 1.6 mm • CVVS 1.25 mm
M-NET transmission
line
Power needs to be supplied to the M-NET circuitry of this device. Use an outdoor unit or a separately
purchased power supply unit for the transmission line.
Use electric wire of an appropriate size for the terminal block of this device.
Signal lines
To use an expansion input/output, use a separa tely purchased external input/output adapter.
[Parts to be Purchased Separately]
Name
Power supply unit
PAC-SC51KUA Power supply to the M-NET transmission line
External I/O adapter
PAC-YG10HA
[Commercially available parts]
Name
External 24 VDC
Supplies power when to use the DIDO controller or
power source
transistor output.
Requires commercially available relay device
Relay device
depending on the electric specifications with an
external device.
4 (*M4: ISO metric screw thread)
Ripple noise: Lower than 200 mVp-p
Compatible specification
Authorized or CE marked products
Subject to regulations: - IEC60950 (or EN60950)
- CISPR22/24 (or EN55022/24)
- IEC61000-3-2/3-3 (or EN61000-3-2/3-3)
When using transistor output (including extension output) for the 24 VDC output of this device, increase
the capacity to match the number used.
• 1 set used: 0.3 ADC (Minimum) • 2 sets used: 0.4 ADC (Minimum) • 3 sets used: 0.5 ADC (Minimum)
• 4 sets used: 0.6 ADC (Minimum) • 5 sets used: 0.7 ADC (Minimum) • 6 sets used: 0.8 ADC (Minimum)
* The increase of the power supply capacity is 0.1 ADC for every set.
* CPEV: PE insulated PVC jacketed shielded communication cable
* CVVS: PVC insulated PVC jacketed shielded control cable
PE: Polyethylene
PVC: Polyvinyl choloride
Electric wire size ···· (1) Solid wire: 0.65 mm (AWG21) -
(2) Stranded wire: 0.75 mm
Model
Connection adapter for using an expansion
input/output
Application
CONTROLLER
Specification
2
(AWG18)
2
2
to 2 mm
(AWG 16 to 14)
2
(AWG18) - 1.25 mm
Single strand: At least
Application
This is not required when power is to be
supplied from an outdoor unit.
This is required when an expansion input/
output is used.
Refer to "Power supply for this device" in "Required
Part" above for the power supply capacity.
1.2 mm (AWG16)
2
(AWG16)
0.18 mm
Remark
Remark
3 - 67