3. System remote controller
1. Power supply to AG-150A
AG-150A needs DC power supply of 24V and M-NET (24~32V); the former is for centralized control transmission use and the
latter is for AG-150A's operating and LAN function use.
(1). Power supply unit PAC-SC51KUA is the recommended power supplier for AG-150A. The basic scheme is as follows.
For details, please refer to Power supply unit PAC-SC51KUA.
CENTRALIZED CONTROLLER AG-150A
Centralized controller
AG-150A
24VDC
PAC-SC51KUA
(TB2 and TB3 used)
NOTE: For information about AG-150A connected with the expansion controller, refer to the following section(s):
3-6. Expansion Controller [PAC-YG50ECA]
M-NET
HBC controller
TB2
HBC controller
Fig. 1 AG-150A and PAC-SC51KUA basic scheme.
CONTROLLER
M-NET
ME remote
controller
M-NET
ME remote
controller
ME remote
controller
LOSSNAY unit
PZ-52SF
3 - 23