Mitsubishi Electric PURY-WP-YJM-A Data Book page 8

Table of Contents

Advertisement

1. SPECIFICATIONS
Model
Power source
Cooling capacity
(Nominal)
*2 Power input
*2 Current input
Heating capacity
(Nominal)
*2 Power input
*2 Current input
External finish
External dimension H x W x D
Net weight
Heat exchanger
Water Volume
FAN
Type x Quantity
*4 External static press.
Motor Type
Motor output
Driving mechanism
Air flow rate
Sound pressure level (measured in anechoic room)
Insulation material
Air filter
Protection device
Refrigerant control device
Connectable outdoor unit/HBC controller
Water piping diameter
Inlet
*5 *6 Outlet
Field drain pipe size
Drawing
External
Wiring
Refrigerant cycle
Standard attachment
Document
Accessory
Optional parts
Control box replace kit
Remarks
Notes :
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°FD.B./66°FW.B.), Outdoor: 35°CD.B. (95°FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°FD.B.), Outdoor: 7°CD.B./6°CW.B. (45°FD.B./43°FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Please group units that operate on 1 branch.
PEFY-WP40VMS1-E
1-phase 220-230-240 V 50/60
Hz
*1 kW
4.5
*1 kcal/h
3,900
*1 BTU/h
15,400
kW
0.090
A
0.73
*3 kW
5.0
*3 kcal/h
4,300
*3 BTU/h
17,100
kW
0.070
A
0.62
Galvanized steel plate
mm
200 x 990 x 700
in.
7-7/8 x 39 x 27-9/16
kg (lbs)
25 (56)
Cross fin (Aluminum fin and
copper tube)
L
1.0
Sirocco fan x 3
Pa
<5> - 15 - <35> - <50>
mmH
O
<0.5> - 1.5 - <3.6> - <5.1>
2
DC motor
kW
0.096
Direct-driven by motor
(Low-Mid-High)
3
m
/min
9.5 - 11.0 - 13.0
L/s
158 - 183 - 217
cfm
335 - 388 - 459
(Low-Mid-High)
*2 dB <A>
30-32-35
EPS, Polyethylene foam, Ure-
thane foam
PP honeycomb fabric.
Fuse
-
HYBRID CITY MULTI/CMB-
WP-V-G
in.
Rc 3/4 screw
in.
Rc 3/4 screw
mm (in.)
O.D.32 (1-1/4)
KD94T794X01
KD94T793X01
-
Installation Manual, Instruc-
tion Book
Insulation pipe for water pipe,
Washer, Drain hose, Tie band
PAC-KE70HS-E
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
INDOOR UNITS
PEFY-WP50VMS1-E
1-phase 220-230-240 V 50/60
Hz
5.6
4,800
19,100
0.090
0.77
6.3
5,400
21,500
0.070
0.66
Galvanized steel plate
200 x 1,190 x 700
7-7/8 x 46-7/8 x 27-9/16
27 (60)
Cross fin (Aluminum fin and
copper tube)
1.7
Sirocco fan x 4
<5> - 15 - <35> - <50>
<0.5> - 1.5 - <3.6> - <5.1>
DC motor
0.096
Direct-driven by motor
(Low-Mid-High)
12.0 - 14.0 - 16.5
200 - 233 - 275
424 - 494 - 583
(Low-Mid-High)
30-33-36
EPS, Polyethylene foam, Ure-
thane foam
PP honeycomb fabric.
Fuse
-
HYBRID CITY MULTI/CMB-
WP-V-G
Rc 3/4 screw
Rc 3/4 screw
O.D.32 (1-1/4)
KD94T794X01
KD94T793X01
-
Installation Manual, Instruc-
tion Book
Insulation pipe for water pipe,
Washer, Drain hose, Tie band
PAC-KE70HS-E
Unit converter
kcal
=kW x 860
BTU/h =kW x 3,412
3
cfm
=m
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.