Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01

6.4.2.4 Reset time

The reset time represents the I-component of a controller. The I component of a controlling leads to
an integral approximation of the actual value to the set point. Short integral means that the
controller has a strong I component.
A short integral has the effect that the manipulated variable is quickly approaching the proportional
band corresponding to the set control value. A large integral causes a slow approach to this value.
Important to note is that a too small reset time can cause an overshoot. Basically can be mentioned,
slower systems need a greater reset time.

6.4.2.5 Send control value cyclic

The pa a ete "e d o t ol alue
time shifts between two values can be also parameterized.
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
56
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
li
auses a
li se di g of the a tual o t ol alue. The