Operating Modes & Setpoints - MDT SCN-RT1GW.01 Technical Manual

Table of Contents

Advertisement

Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01
6.3.2 Operating modes & Setpoints
The following figure shows the available settings for the operating modes and the setpoints:
Figure 9: Settings operating modes & setpoints
Die folgende Tabelle zeigt die einzelnen Betriebsarten und deren Einstellbereiche:
ETS-text
Basis comfort setpoint
Night reduction
Standby reduction
Setpoint frost protection
Setpoint heat protection
Table 22: Operating modes & setpoints
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
39
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de
Dynamic range
[default value]
18,0°C – 25,0°C
[21,0°C]
Lowering in K
0 K – 10,0 K
[3,0 K]
Lowering in K
0 K – 10,0 K
[2,0 K]
3°C – 12°C
[7°C]
24°C – 40°C
[35°C]
comment
The basis comfort setpoint is the reference
point of the control.
Lowering of the temperature by choosing
the operating mode night.
Relative to the basis comfort setpoint.
gets activated when no other operating
mode was chosen
The lowering is relative to the basis
comfort setpoint.
Setpoint of the operating mode frost
protection.
indicated by an absolute value
Setpoint of the operating mode heat
protection.
indicated by an absolute value