Technical Manual
Room Temperature Controller
4.4.2.7 Operating mode after reset
The following picture shows the available settings:
Figure 11: Settings – Operating mode after reset
The table shows the available settings:
ETS-text
Operating mode after
reset
Table 22: Settings – Operating mode after reset
This parameter defines the operating mode, which shall be adjusted after a bus power return. The
controller can start with the "Comfort" mode or with the "Standby" mode. In both cases, the
parameterized set point will be restored. By using setting "Hold old state and set point", the
controller restores the old operating mode and the set point, which was active before the reset. It
must be pointed out, that the controller has no settings in its memory in case of an initial operation.
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
20
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
[SCN-RT1xPx.01]
Dynamic range
[default value]
▪ Comfort with parameterized
setpoint
▪ Standby with parameterized
setpoint
▪ Hold old state and setpoint
Comment
Setting which operating mode is
to be activated after a bus
voltage return.