There are no integrated temperature controllers at this device. The temperature sensor has its areas of use at the measuring of temperatures for other controllers. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
The room temperature sensor, SCN-TS1UP.01, is for flush-mounting. It contains also of a bus- connection, a programming button and a programming LED. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
If you choose the SCN-TS1UP.01 as device at the setup general, only the menus setup general, temperature measurement and alarm/messages will be shown. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
2.7 Starting up After wiring the allocation of the physical address and the parameterization of every channel follow: (1) Connect the interface with the bus, e.g. MDT USB interface (2) set bus power up (3) Press the programming button at the device(red programming LED lights)
Disable cooling 1 Bit Heating request Send request 1 Bit Cooling request Send request 1 Bit Heating/Cooling 0=Heating 1 Bit switchover 1=Cooling MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 10
The flags allocates the function of the objects in the programming thereby stands C for communication, R for Read, W for write, T for transmit and U for update. * from version 1.2 MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
When this hardware is selected, only the menus “Setup general“(4.1), “Temperature measurement” (4.2) and “Alarm/Messages” (4.3) are shown and can be parameterized. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
▪ 80 % intern/ 20% extern ▪ … ▪ 100% extern Table 4: Parameter Temperature measurement The effects of the settings are described at the following page. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 13
1 Bit sends an error, when the external sensor sends no value for more than 30min Table 7: Communication objects external sensor MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Message if value < 1°C-25°C Dynamic range of the lower message [13°C] Adjustment possible if messages are activated Table 8: Parameter Alarm/Messages MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 15
Send the achievement of the higher reporting limit Below message value 1 Bit Send the achievement of the lower reporting limit Table 10: Communication objects messages MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
There are a lot of settings, which can help to achieve this aim. The settings depend to the adjusted controller type. By choosing the setting “controller off”, no further settings are possible. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
24°C – 40°C Setpoint of the operating mode heat [35°C] protection. indicated by an absolute value Table 12: Operating modes & setpoints MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 18
Activation of the operating mode heat protection Mode frost/heat protection 1 Bit Activation of the operating mode frost/heat protection Table 15: Communication object operating mode frost/heat protection MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 19
Frost-/ Heat protection Comfort Night Frost-/Heat protection Standby Frost-/Heat protection Comfort Table 17: Example switchover of the operating modes via 1 Bit MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 20
If you heat at the comfort mode, the communication object will send the value 20 (for heating) +1 (for the comfort mode) =21. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 21
1 Byte Selection of the operating mode Table 22: Communication objects for the operating mode switchover * from Version 1.2 MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 22
It must be pointed out, that the controller has no settings in its memory in case of an initial operation. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Specifying a new value is possible by calling the object “Setpoint comfort”. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 24
Movement of the setpoint depending to the current adjusted basic comfort setpoint Actual setpoint 2 Byte Readout of the actual adjusted setpoint Table 25: Communication objects setpoint offset MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
1 Bit blocks the control value heating Cooling disable object 1 Bit blocks the control value cooling Table 27: Communication objects blocking objects MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
So when the value is between the adjusted guiding values (w & w ) the setpoint is increased or decreased. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 28
If the outside temperature reaches the adjusted maximum of 38°C, the setpoint will be 32°C and behave this value even if the temperature would continue to rise. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
So, when the basic comfort setpoint is set to 21°C and the dead zone is set to 3K, the setpoint for heating is 21°C and the setpoint for cooling is 24°C. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 30
Dead zone between heating and cooling: 3K Increase and Reduction standby: 2K Increase and Reduction night: 4K Figure 19: Example dead zone MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
PI control switching or 2-step control, the communication object will have the size of 1 Bit, because the communication object can only assume the states on or off. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
▪ No Use additional level Activation of an additional level ▪ Yes available, only for heating (4.5.6) Table 35: PI control continuous MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 34
The parameter “Send control value cyclic” causes a cyclic sending of the actual control value. The time shifts between two values can be also parameterized. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Individual parameterization available by ▪ Underfloor heating (5K/240 “Adjustment via control parameter” min) ▪ Split Unit (4K/90min) ▪ Adjustment via control parameter MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 36
7,5min and switched off for 2,5min. In principle you can say each carrier the system, each bigger the cycletime. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
The 2-step control is used in situations, where the control value can only have two conditions and the controlled temperature can alternate a bit more. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 38
This can generate a fast consumption of the control value. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
The controller switches on at the normal point for switching off and switches off at the normal point for switching on. 4.5.6 Additional level The following settings are available at the ETS-Software: Figure 25: Additional level MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 40
Number Name Length Usage Control value additional 1 Bit control value for the additional level heating Table 39: Communication object additional level MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 41
The following illustration shows the combination of the basic level and the additional level: Figure 26: Combination of basic and additional level MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
4 Pipe system must be chosen. Furthermore it is possible to choose between an automatic and a manual switch over. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 43
(as described from 4.5.2 to 4.5.4). The following illustration shows the setting option for a 2 Pipe system: Figure 28: 2 Pipe system MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 44
“4.5 controller settings”. The following illustration shows the setting options for a 4 Pipe system: Figure 29: 4 Pipe system MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Page 45
Number Name Length Usage Heating/Cooling switchover 1 Bit Switchover between heating and cooling 1=heating; 0=cooling Table 41: Communication object heating and cooling MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
All activities on the device should only be done by an electrical specialist. The county specific regulations and the applicable EIB-directives have to be observed. MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
Three different controller types can be chosen for the control value. These controller types are described for the heating process by the following illustrations. 6.4.1 2-Step control MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Phone: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...