MDT SCN-RT1GW.01 Technical Manual page 52

Table of Contents

Advertisement

Technical Manual Glass Room Temp. Contr. SCN-RT1Gx.01
The dependent setpoints for heating and cooling, so the setpoints for the operating modes standby
and night, can be parameterized individually at the controller type heating and cooling. So you can
set different values for the nigh and standby reduction/increase at heating and cooling. These
setpoints are calculated in dependence to the basic comfort setpoints.
The setpoints for the frost and heat protection are individually from the dead zone and the other
setpoints.
The following illustration shows the correlations between dead zone and the setpoints for the single
operating modes.
The following settings are made for this example:
Basic comfort setpoint: 21°C
Dead zone between heating and cooling: 3K
Increase and Reduction standby: 2K
Increase and Reduction night: 4K
Figure 19: Example dead zone
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
52
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scn-rt1gs.01

Table of Contents