Within 300mm
Drain hose
Ceiling
Instruction
☆ The slant gradient of the attached drain hose should
be within 75mm so that the drain hole doesn't has to
endure the unnecessary outside force.
☆ Please install the drain hose according to the
following process if several drain hoses join together.
Above100mm
The specs of the selected join drain hose should fits the running capacity of the unit.
☆ Check the smoothness of drain after installation.
☆ Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
☆ Check the drain in the state of refrigerating after installation of the electric circuit.
[ Way of immiting ]
Drain vent for repair use (plastic
stopper is included) (drain the water
in waterspout by this outlet vent)
Roof
Clamp(attachment)
Above100mm
< Immiting water from the outlet
vent terminal >
Hoisting stand
1-1.5m
below 280mm
Drain raising
hose
220mm
Drain hose(attachment)
Drain hose
Test hole
< Immiting water from the rest hole >
Plastic water pot (The length of the
pipe should be about 100mm.)
T-tie in join drain hose
Test hole cover
37