LOCATION OF ICVD CONDENSING UNITS
The location selected for the ICVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
ICVD0895/ICVD0996/ICVD1095/ICVD1096/ICVD1495/
•
ICVD1496/ICVD1895/ICVD1896/ICVD2195/ICVD2096
Only
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 130°F (54.4°C).
ICVD695/ICVD0696/ICVD1195/ICVD2095/ICVD2096/
•
ICVD3095 Only
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 120°F (48.9°C).
•
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
•
The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
30